Date Text
2002-07-26 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION MAKE ANY NECESSARY CHANGES
 IN THE PLANS AND RESUBMIT FOR REVIEW:
  
 1} PLEASE PROVIDE LOAD CALCULATIONS
 INCLUDING ALL ADDITIONAL LOADS PER
 220-3(C)(1).
  
 2} NEW BEDROOM CIRCUITS TO BE AFCI
 PROTECTED PER 212-12.
  
 3} PLEASE SHOW THE LOCATIONS OF THE
 AHU'S AND DISCONNECTS ON THE ELECTRICAL
 PLANS.
  
 4} PLEASE NOTE THAT THE #6 GROUND
 BETWEEN THE METER AND THE MAIN
 DISCONNECT,ALTHOUGH EXISTING,IS
 CREATING A PARALLEL PATH TO GROUND WITH
 THE NEUTRAL AND SHOULD BE REMOVED.SEE
 250-6(B)(1),1999 NEC.
  
 5} PLEASE INDICATE WHICH WORK IS NEW AND
 WHICH IS EXISTING.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL:
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392