| Plan Review Notes For Permit 02070869 |
| Permit Number |
02070869 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-07-26 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE PROVIDE THE FOLLOWING | | | INFORMATION MAKE ANY NECESSARY CHANGES | | | IN THE PLANS AND RESUBMIT FOR REVIEW: | | | | | | 1} PLEASE PROVIDE LOAD CALCULATIONS | | | INCLUDING ALL ADDITIONAL LOADS PER | | | 220-3(C)(1). | | | | | | 2} NEW BEDROOM CIRCUITS TO BE AFCI | | | PROTECTED PER 212-12. | | | | | | 3} PLEASE SHOW THE LOCATIONS OF THE | | | AHU'S AND DISCONNECTS ON THE ELECTRICAL | | | PLANS. | | | | | | 4} PLEASE NOTE THAT THE #6 GROUND | | | BETWEEN THE METER AND THE MAIN | | | DISCONNECT,ALTHOUGH EXISTING,IS | | | CREATING A PARALLEL PATH TO GROUND WITH | | | THE NEUTRAL AND SHOULD BE REMOVED.SEE | | | 250-6(B)(1),1999 NEC. | | | | | | 5} PLEASE INDICATE WHICH WORK IS NEW AND | | | WHICH IS EXISTING. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL: | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/659-8096 EXT. 8392 |
|