Plan Review Notes
Plan Review Notes For Permit 02070869
Permit Number 02070869
Review Stop B
Sequence Number 1
Notes
Date Text
2002-08-14 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 02070869
 ADD: 3626 N FLAGLER DR
 CONT: HINKLEY CONSTRUCTION
 TEL: (561)832-3310
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
  
 1) CITY CODE CHAPTER 12 DEALS WITH THE
 CITY FLOOD PREVENTION & CONTROL.AS INDIC
 ATED ON YOUR SURVEY, THIS LOT IS LOCATED
 IN A "A5" FLOOD ZONE. THIS REQUIRES A
 FINISH FLOOR ELEVATION ON ALL NEW WORK
 OF 7'-6".
  
 SEE CITY CODE FOR "SUBSTANTAIL IMPROVE-
 MENTS",AND PROCEDURES FOR APPLYING FOR
 VARIANCE.A COPY OF CHAPTER 12 AND VARIAN
 CE WILL BE ATTACHED.
  
 UNLESS THE CONSTRUCTION BOARD OF ADJUST-
 MENT AND APPEALS REVIEWS AND APPROVES
 THE VARIANCE THE FINISH FLOOR OF HABITAB
 LE SPACE SHALL BE 7'-6" NVGD.
  
 THE EXISTING GARAGE FLOOR IS STILL ANOTH
 ER ISSUE, BEING THAT IT HAS A FINISH
 FLOOR 5.47 NVGD. FEMA PART 60.3(C)(5)
 REQUIRES FOR ALL NEW CONSTRUCTION AND
 SUBSTANTIAL IMPROVEMENTS, THAT ARE FULLY
 ENCLOSED AREAS BELOW THE LOWEST FLOOR
 THAT ARE USABLE SPACE SOLEY FOR PARKING
 OF VEHICLES, BUILDING ACCESS OR FOR
 STORAGE IN AND AREA OTHER THAN A BASE-
 MENT AND WHICH ARE SUBJECT TO FLOODING
 SHALL BE DESIGNED TP AUTOMATICALLY
 EQUALIZE HYDROSTATIC FLOOD FORCES ON
 EXTERIOR WALLS BY ALLOWING FOR THE ENTRY
 AND EXIT OF FLOOD WATERS. DESIGNS FOR
 MEETING THIS REQUIREMENT MUST EITHER BE
 CERTIFIED BY A REGISTERED PROFESSIONAL
 ENGINEER OR ARCHITECT OR MEET OR EXCEED
 THE FOLLOWING MINIMUM CRITERIA:
 A MINIMUM OF (2) OPENINGS HAVING A TOTAL
 NET AREA OF NOT LESS THAN ONE SQUARE IN
 CH FOR EVERY FOOT OF ENCLOSED AREA SUB-
 JECT TO FLOODING SHALL BE PROVIDED. THE
 BOTTOM OF ALL OPENINGS SHALL BE NO HIGH-
 ER THAN ONE FOOT ABOVE GRADE. OPENINGS
 MAYBE EQUIPPED WITH SCREENS,LOUVERS,
 VALVES, OR OTHER COVERINGS OR DEVICES
 PROVIDED THAT THEY PERMIT THE AUTOMATIC
 ENTRY AND EXIT OF FLOODWATERS.
  
 2) 3401.7.6 WHEN REPAIRS AND ALTERATIONS
 AMOUNTING TO MORE THAN 50% OF THE VALUE
 OF THE EXISTING BUILDING ARE MADE IN ANY
 12 MONTH PERIOD, THE BUILDING OR STRUC-
 TURE SHALL BE MADE TO CONFORM TO THE
 REQUIREMENTS FOR A NEW BUILDING OR EN-
 TIRELY BE DEMOLISHED, SEE EXCEPTIONS.
  
 3) ROOM 105, THE NEW ADDITION SHALL BE
 6'-6" FROM THE PROPERTY LINE, THIS
 CREATES A PROBLEM, TABLE 600. 3'-10'
 ALLOWS FOR 20% WALL OPENINGS, FROM 10'-
 20' THE ALLOWABLE OPENING SIZE IS 40%.
 EAST AND NORTH ELEVATIONS ARE OVER
 ALLOWABLE OPENING AREA. A SECOND
 VARIANCE REQUEST TO THE BOARD OF
 ADJUSTMENT AND APPEALS MAY BE ONE SOLU-
 TION.
  
 4)PROVIDE ENERGY CALCULATIONS AND
 EQUIPMENT SIZING CALCULATIONS (MANUAL J)
 AS REQUIRED BY THE 2001 FLORIDA ENERGY
 EFFICIENTCY CODE FOR BUILDING CONSTRUC-
 TION.
  
 SHEET S-3 MAKE CORRECTIONS STATING THE
 FL BLDG CODE NOT STANDARD OR SOTHERN
 BUILDING CODE.
  
 5)FIGURE 1606 WIND-BORNE DEBRIS
 REGION; INDICATES THAT W.P.B. CITY OF IS
 LOCATED IN THE 140 MPH ZONE. PLANS ARE
 TO INDICATE THIS.
  
 6)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
  
 7) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED. MISSING REPORTS:
 A) WINDOWS
 B) DOORS
 C) MULLIONS
 D) ROOFING ASSEMBLIES
 E) STORM SHUTTERS
  
 8) PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING.
 FBC 1606.1.4.
  
 9)FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 10) 1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 11) 1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 12)1707.3.1 JOIST HANGERS, FRAMING
 ANCHORS & SIMILAR DEVICES SHALL BE TEST-
 ED IN ACCORDANCE W/ ASTM D 1761 & BE
 LABELED AND LISTED FOR THEIR LOAD CARRY-
 ING CAPACITY.
  
 13)FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
  
 14)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026