Plan Review Notes
Plan Review Notes For Permit 02070594
Permit Number 02070594
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2002-07-12 00:00:001) PLEASE PROVIDE COPY OF WORK CONTRACT.
 VALUE OF JOB APPEARS TO BE TOO LOW.
  
 2) A REVIEW OF THE ARCHITECTURAL PLANS
 INDICATE THAT THE BUILDING WILL BE
 AN ASSEMBLY OCCUPANCY WITH A SIGNIFICANT
 OCCUPANT LOAD. THE PLANS DO NOT
 INDICATE A VOICE EVACUATION SYSTEM
 WITHIN THIS SPACE. HORN STROBES ARE
 SHOWN ON THE DEVICE LEGEND.
  
 3) MEN'S ROOM 205 APPEARS TO BE MISSING
 A VISIBLE DEVICE.
  
 4) THE CUT SHEET DEVICES PROVIDED WITH
 PLANS HAVE SPEAKER STROBES IDENTIFIED
 AS BEING USED.
  
 5) PLEASE INDICATE WHAT THE VOICE
 EVACUATION MESSAGE PORTION OF THE FIRE
 ALARM SYSTEM WILL SAY.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910