| 2003-03-27 00:00:00 | | | | *** ISSUED PERMIT*** | | | -PLAN REVIEW HISTORY- | | | | | | PERMIT PHASE-I02070564 | | | PHASE-II 03011849 | | | ADDRESS: 1100 ELIZABETH AVE | | | CONT: GLACE& CO. | | | TELL # (561) 585-5564 | | | | | | THE ATTACHED COMMENTS ARE PART OF THE | | | PERMIT AND PLAN REVIEW PACKAGE AND ARE | | | NOT TO BE REMOVED FROM THE ISSUED SET OF | | | PLANS.104.2.1.2 ADMINISTRATIVE CODE. | | | | | | ****PROVISO**** | | | | | | MECHANICAL PERMIT REQUIRED: SECTION | | | 411.5.4 REPAIR GARAGES, | | | SHALL BE CONTINUOUSLY VENTILATED BY A | | | MECHANICAL SYSTEM WITH POSITIVE MEANS OF | | | BOTH INLET AND EXHAUST OF AT LEAST 0.75 | | | CFM PER SQ FT (0.0038 M3/M2) OF FLOOR | | | AREA, CONTROLED FROM A LOCATION CLOSE TO | | | THE ENTRANCE DOOR. | | | BUILDING PLAN REVIEW | | | JIM WITMER |
|