2003-03-27 00:00:00 
 *** ISSUED PERMIT***
 -PLAN REVIEW HISTORY-
  
 PERMIT PHASE-I02070564
 PHASE-II 03011849
 ADDRESS: 1100 ELIZABETH AVE
 CONT: GLACE& CO.
 TELL # (561) 585-5564
  
 THE ATTACHED COMMENTS ARE PART OF THE
 PERMIT AND PLAN REVIEW PACKAGE AND ARE
 NOT TO BE REMOVED FROM THE ISSUED SET OF
 PLANS.104.2.1.2 ADMINISTRATIVE CODE.
  
 ****PROVISO****
  
 MECHANICAL PERMIT REQUIRED: SECTION
 411.5.4 REPAIR GARAGES,
 SHALL BE CONTINUOUSLY VENTILATED BY A
 MECHANICAL SYSTEM WITH POSITIVE MEANS OF
 BOTH INLET AND EXHAUST OF AT LEAST 0.75
 CFM PER SQ FT (0.0038 M3/M2) OF FLOOR
 AREA, CONTROLED FROM A LOCATION CLOSE TO
 THE ENTRANCE DOOR.
 BUILDING PLAN REVIEW
 JIM WITMER