Plan Review Notes
Plan Review Notes For Permit 02070564
Permit Number 02070564
Review Stop B
Sequence Number 2
Notes
Date Text
2003-02-14 00:00:00BUILDING PLAN REVIEW
 PERMIT:02070564
 ADD: 1100 ELIZABETH AVE
 CONT: GLACE
 TEL: (561)585-5564
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) COMMENT #2, FOR A TYPE V BUILDING
 0-3' FROM PROPERTY LINE REQUIRES A 3HR
 WALL. GROUND FLOOR PLAN INDICATES THE
 PROPERTY LINE WALL IS SECTION 8/A3.
 THIS SECTION INDICATES A H.M. DOOR?
 SEE TABLE 600 FOR RATINGS.
  
 2) COMMENT# 3 THE USAGE TO BE AUTO
 REPAIR GARAGE. SEE 411.5.3 FOR REPAIR
 GARAGES, SEE TABLE 704.1 REPAIR GARAGES
 TO HAVE A 2 HR RATING FROM OTHER OCCU-
 PANCIES, OFFICE/ RESIDENTIAL! DOOR LEAD-
 ING INTO EXISTING BUILDING, 1 1/2 HR
 PROTECTIVE. IF OTHER OPENINGS PROVIDE
 ADDITIONAL INFORMATION. SEC. 411.5.4
 REPAIR GARAGES SHALL BE CONTINUOUSLY
 VENTILATED BY A MECHANICAL SYSTEM WITH
 POSITIVE MEANS FOR BOTH INLET AND EX-
 HAUST OF AT LEAST 0.75 CFM PERSQ FT
 (0.0038 M3/S/M2) OF FLOOR AREA, CONTROLL
 ED FROM A LOCATION CLOSE TO THE ENTRANCE
 DOOR.
  
 3) COMMENT# 6 THE NEW STRUCTURE DOES NOT
 INDICATE ANY TYPE OF SHEAR WALL CONSTRUC
 TION, WHAT IS TO STOP RACKINGIF THE
 STEEL STRUCTURE IS NOT TIED TO THE EXIST
 ING STRUCTURE? INDICATE EITHER SHEER
 WALLS OR A STRUCTURAL CONNECTION TO THE
 EXISTING BUILDING, WHAT IS THE EXISTING
 BUILDING CONSTRUCTED OF?
  
 4) COMMENT# 7 PROVIDE THE COMPLETE PRO-D
 UCT TESTING FOR THE ROOF ASSEMBLIES,
 MISSING THE MECHANICAL ATTACHMENT OF
 INSULATION BOARD TO THE METAL DECKING.
 MISSING THE ATTACHMENT OF THE METAL DECK
 ING TO THE 8" CS/JOIST.
  
 5) COMMENT# 14 MISSING REPORT FOR GLASS
 BLOCK, DETAIL NOT A TESTING REPORT FOR
 LARGE MISSLE IMPACT TESTING IF THE WALL
 THICKNESS IS TO THIN, THEN STORM SHUT-
 TERS AND TESTING REPORTS WILL BE NECESS
 ARY. ALSO THE INFORMATION REQUIRED :
 FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)659-8096 X 8412
 FAX: (561)659-8026


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved