2002-12-23 00:00:00BUILDING PLAN REVIEW
 PERMIT: 02070564
 ADD: 1100 ELIZABETH AVE
 CONT: GLACE & COMPANY
 TEL: (561)585-5564
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 NOTE: LOCATED IN A FIRE ZONE
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) WHAT TYPE BUILDING TYPE VI OR TYPE V
 BUILDING?
 TABLE 600 EXTERIOR NON BEQARING WALLS,
 0-3" FROM PROPERTY LINE.
 TYPE V 3HR WALL, 704.5 PARAPETS 18".
 TYPE VI 1HR WALL
  
 3) 301.2 OCCUPANCY OR USE CATEGORIES.
 WHAT WILL THIS SPACE BE USED FOR?
 IF FOR ENCLOSED PARKING GARAGES SEE
 SECTION 411.4.
 IF THIS AREA IS TO BE REPAIR GARAGE
 (REINSTALL LIFT) SEE 411.5 REPAIR
 GARAGES.
  
 4) WHAT WILL THE OCCUPANCY BE OF THE
 EXISTING BUILDING FIRST FLOOR AND SECOND
 FLOOR?
  
 5) THIS ADDITION INDICATES A-3 /1 WOOD
 STUD WALL AS A TEMP WALL. F 102.1 NO
 TYPE VI IN FIRE DISTRICT.
  
 6) PLEASE INDICATE HOW THIS ADDITION IS
 ATTACHED TO EXISTING STRUCTURE?
  
 7) MANUFACTURES INFORMATION ON "EPICORE
 ROOFING SYSTEM", ALLOWABLE SPANS,
 IMPOSED LOADS, WELDING INFORMATION,
 AND INFO FOR CONCRETE DECK AND REINFORCE
 MENT.
  
 8) SHEET S.1 DETAIL# 6 INDICATES 4 5/8"
 EXSPANSION ANCHORS THE IMPOSED LOADS NOT
 GIVEN! HAS A DERATING FACTOR BEEN FIG-
 URED IN FOR THE CLOSENESS TO EDGE
 DISTANCE?
  
 9) 1012.1.1. EGRESS DOORS ARE REQUIRED
 SWING DOORS.
  
 10) SEE 1017 FOR THE NUMBER OF EXITS
 REQUIRED FOR STORAGE, (2 EXITS REQUIRED)
  
 11) FIGURE 1606 WIND-BORNE DEBRIS
 REGION; INDICATES THAT W.P.B. CITY OF IS
 LOCATED IN THE 140 MPH ZONE. PLANS ARE
 TO INDICATE THIS.
  
 12) FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 13)1606.1.4(1) IN WIND BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES
 POSITIVE PRESSURE IN BUILDINGS SHALL BE
 ASSUMED TO BE OPENINGS UNLESS SUCH
 GLAZING IS IMPACT RESISTANT OR PROTECTED
 WITH AN IMPACT RESISTANT COVERING MEET-
 ING THE REQUIREMENTS OF SSTD 12, ASTM
 E 1886 AND ASTM E 1996 OR MIAMI-DADE.
  
 1) GLAZED OPENINGS LOCATED WITHIN 30 FT
 OF GRADE SHALL MEET THE REQUIREMENTS OF
 LARGE MISSLE TEST.
  
 14)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED.MISSING REPORTS:
 A) GLASS BLOCK
 B) SKY LIGHTS
 C) ROLL UP GARAGE DOORS
 D) SWING DOORS
 E) ROOFING ASSEMBLIES
 F) STORM SHUTTERS
 1707.4.3 EACH EXTERIOR DOOR
 ASSEMBLY NOT COVERED BY 1707.4.2
 (GLAZED DOORS) SHALL BE LISTED AND TEST-
 ED FOR A PERIOD EQUAL TO THE QUANITY
 3600/ V WHERE THE TIME PERIOD IS IN
 SECTIONS AND V IS IN MILES PER HR TAKEN
 FROM FIGURE 1606. THE TIME PERIOD SHALL
 ALSO INCLUDE A 10 SECOND PERIOD AT A
 LOAD EQUAL TO 1.5 TIMES THE DESIGN
 PRESSURE. DADE COUNTY & SBCCI REPORTS
 ARE ACCEPTED.
  
 15) 1707.4.4.1 ANCHOR REQUIREMENTS:
 WINDOW & DOOR ASSEMBLIES SHALL BE ANCHOR
 ED IN ACCORDANCE WITH THE PUBLISHED
 MANUFACTURER'S RECOMMENDATIONS TO
 ACHIEVE THEDESIGN PRESSURE SPECIFIED.
 SUBSTITUTE ANCHORING SYSTEM USED FOR
 THE SUBSTRATE NOT SPECIFIED BY THE
 FENESTRATION MANUFACTURER SHALL PROVIDE
 EQUAL OR GREATER ANCHORING AS DEMONSTRA-
 TED BY ACCEPTED ENGINEERING PRACTICES.
  
 15) FL BLDG 1909.3 (EXEPTION# 2)
 CONCRETE SLABS ON GRADE CONTAINING 6X6/
 W1.4XW1.4 WELDED WIRE REINFORCEMENT
 FABRIC LOCATED IN THE MIDDLE TO THE
 UPPER 1/3RD OF THE SLAB SHALL BE SUP-
 PORTED BY APPROVED MATERIALS OR SUPPORTS
 AT SPACING NOT TO EXCEED 3 FT OR IN
 ACCORDANCE WITH MANUFACTURER'S SPEC.
  
 16) 1503.4.4 PROTECTION AGAINST DECAY &
 TERMITES. CONDENSATE LINES & ROOF DOWN
 SPOUTS SHALL DISCHARGE AT LEAST 1 FT.
 AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EX-
 TENSIONS, OR SPLASH BLOCKS.
  
 BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 PHASE (I) TO BE CONSIDERED UNDER THIS
 PERMIT, PHASE (II) TO BE UNDER SEPERATE
 PERMIT. COMMENTS MAY BE ADDRESSED UNDER
 THIS PERMIT TO CORRECT DRAWINGS AND
 CODE ARTICLES.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.