| Plan Review Notes For Permit 02070546 |
| Permit Number |
02070546 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-07-24 00:00:00 | ***************UNSAT *************** | | | | | | 1)NOTE: PLEASE NOTE THAT ALL CIRCUITING | | | NEEDS TO BE PLACED ON PLANS SHOW | | | CORRELATING PANEL SCHEDULES. | | | PLEASE NOTE A PANEL IN ONE TENANT SPACE | | | MAY NOT FEED CIRCUITS INTO OTHERS SPACE. | | | | | | 2)NOTE: PLEASE CLARIFY SHOW WINDOW | | | RECPS. PER 210-62 | | | | | | 3)NOTE: PLEASE CLARIFY SIGN CIRCUTIS | | | PER 600-5 | | | | | | 4)NOTE: PLEASE SEE FIRE REVIEW COMMENTS | | | THAT WILL MOST LIKELY AFFECT ELEC PLANS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|