| Plan Review Notes For Permit 02070539 |
| Permit Number |
02070539 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2004-04-05 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 | | | | | | 1.)SEE PREVIOUS LIST, IMPACT | | | PROTECTION REQUIRED.THE PRODUCT | | | APPROVALS SUBMITTED INDICATE THAT THE | | | DOORS DO NOT HAVE IMPACT RATING. | | | | | | 2.)EXTERIOR STAIRS SHALL BE SEPARATED | | | FROM THE INTERIOR BUILDING BY WALLS WITH | | | A FIRE RESISTANCE RATING OF NOT LESS | | | THAN 1 HR, WITH FIXED OR SELF-CLOSING | | | OPENING PROTECTIVES.SHOW COMPLIANCE | | | FOR THE NEW FRENCH DOORS.FBC1006.2.4 | | | | | | 3.)THE ELEVATIONS SHOW SIDELITES, NOT | | | INCLUDED IN THE DOOR PRODUCT APPROVAL. | | | ALSO NEED MULLION PRODUCT APPROVALS. | | | | | | 4.)THE PRODUCT APPROVAL FOR THE | | | COMPONENT APPROVAL - SERIES 1518 | | | DOOR IS INCOMPLETE. |
|