| Plan Review Notes For Permit 02070539 |
| Permit Number |
02070539 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-12-23 00:00:00 | *****CORRECTIONS***** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | REVISION - CHANGE GARAGE DOORS TO | | | FRENCH DOORS | | | | | | 1.)THE PLANS ARE TO BE SEALED BY THE | | | DESIGNER OF RECORD, GORDON BUCK. | | | INCLUDE A COMPLETE TITLE BLOCK. | | | | | | 2.)SUBMIT PRODUCT APPROVALS FOR THE | | | FRENCH DOORS.IMPACT PROTECTION | | | REQUIRED FBC1606.1.4. | | | | | | 3.)CLOUD ALL CHANGES TO EXPEDITE | | | PLAN REVIEW. | | | | | | 4.)THE INFORMATION ON THE "NEW | | | RIGHT ELEVATION" (APPROVED SET) IS NOW | | | MISSING FROM THE "NEW EAST ELEVATION" | | | (REVISION SET).THE INFORMATION | | | DELETED IS IN REGARDS TO FIRE RATED | | | WINDOWS AND EGRESS.ADDRESS. | | | | | | 5.)METAM24 IS NOT IN THE SIMPSON 2003 | | | CATALOG.META24 IS AN EMBEDDED TRUSS | | | ANCHOR WITH A MAX UPLIFT OF 1500. THAT | | | APPLICATION CONFLICTS WITH YOURS, | | | DESIGN UPLIFT EXCEEDS PRODUCT | | | LIMITATIONS.ADDRESS.CHECK ALL | | | CONNECTORS. | | | | | | 6.)PLEASE NOTE THAT THIS CHANGE | | | HAS FAILED ZONING.A BUILDING REVISION | | | CANNOT BE ISSUED WITHOUT ZONING | | | APPROVAL. |
|