Plan Review Notes
Plan Review Notes For Permit 02070539
Permit Number 02070539
Review Stop R
Sequence Number 1
Notes
Date Text
2002-11-14 00:00:00THE NEW APARTMENT IS SUBJECT TO IMPACT
 FEES COLLECTED BY THE COUNTY.THE
 PERMIT PLANS MUST BE STAMPED BY THAT
 OFFICE AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 CALL 561-233-5025 FOR MORE INFORMATION.
  
 SHOW THE FINISH FLOOR ELEVATION RELATIVE
 TO NGVD.
  
 SHEET S2 SHOW THE DESIGN LOADS FOR THE
 FLOORS, HAND AND GUARD RAILS AND
 STAIRS. SEE FBC 1604 AND 1608.
  
 THERE ARE NO DIMENSIONS ON THE FRAMING
 PLANS, S2.
  
 WITH REGARDS TO SECTION 1/S2, WHAT ARE
 THE ASSUMED LOADS FOR THE TWO 1/2"
 BOLTS THAT WILL SUPPORT THE FLOOR
 GIRDER,PARTICULARLY THE F'B OF THE
 WOOD? SEE FBC 104.2
  
 SHOW THE REINFORCED MASONRY
 SPECIFICATIONS IN ACCORDANCE WITH FBC
 2103.1 IE GROUT SPEC, POUR HEIGHT,
 CLEAR SPACE, ETC.
  
 WILL THE MEZZANINE BE FRAMED ON A
 LEDGERAS SHOWN IN SECTION 16/A4 OR
 JOIST HANGERS AS SHOWN IN SECTION A/A3?
  
 THE PLANS DATED 9/26/02 DO NOT HAVE THE
 MEZZANINE INFORMATION SHOWN ON THE
 PLANS DATED 6/24/02.PLEASE COLLATE THE
 PLANS INTO TWO CONCISE SETS.
  
 THE EXTERIOR STAIRS REQUIRE HANDRAILS AT
 EACH SIDE.SEE FBC 1007.5.2.
  
 THE EXTERIOR STAIRS ARE NOT SERVED BY A
 ROOFED 4 1/2 FEET WIDE BALCONY AS
 REQUIRED BY FBC 1006.2.2.
  
 THE WINDOW OPENINGS IN THE AREA
 PRESCRIBED IN FBC 1006.2.4 ARE REQUIRED
 TO BE FIXED 3/4 HOUR RATED ASSEMBLIES.
 (EXTERIOR STAIR)
  
 PLEASE PROVIDE THE CALCULATION REQUIRED
 BY METRO DADE NOA 99-1012.04 FOR USE OF
 THE MORTAR SET SYSTEM NOA 00-0218.03.
  
 PLEASE PROVIDE A RECENT, LEGIBLE,
 SIGNED SEALED AND DATED SURVEY.