2002-10-31 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
  
 1) SHT D-1.0 DEMO NOTES #4, ALL CAPPED
 PLUMBING PIPES SHALL BE INSPECTED PRIOR
 TO COVERING.
 2) SHT A-1.1 GARAGE FLOOR PLAN, MANUF.
 INFO REQUIRED FOR TANKLESS WATER HEATER.
 3) SHT A-1.1 GARAGE FLOOR PLAN, PLEASE
 SUBMIT MANUF. INFO FOR GAS WATER HEATER.
 SHOW DETAIL FOR VENTING. IS THIS A DIR-
 ECT VENT SYSTEM?
 4) SHT E-1 PLUMBING NOTES #8, AIR CHAMB-
 ERS ARE NOT APPROVED. PLEASE DELETE REF-
 ERENCE. WATER HAMMER ARRESTORS TO BE IN-
 STALLED PER 604.9. W/M - DISHWASHER -
 ICE MAKER.
 5) SHT E-1 SANITARY RISER DIAGRAM DOES
 NOT MEET CODE. PLEASE SUBMIT A RISER DIA
 GRAM THAT MEETS CODE REQUIREMENTS. (SEE
 ATTACHED SHEET FOR EXAMPLE)
 6) ENCLOSED USABLE SPACE SHALL BE PER-
 MITTED UNDER STAIRS PROVIDED THE SPACE
 IS SEPARATED FROM THE STAIR ENCLOSURE BY
 THE SAME FIRE RESISTANCE AS THE EXIT EN-
 CLOSURE. SEC 1006.1.4 EXCEPTION (1).
 7) GAS PERMIT REQUIRED. SEE FOLLOWING
 GAS PERMIT APPLICATION REQUIREMENTS.
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 GAS CODE.
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 3) TYPE OF GAS, (LP OR NATURAL)
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 FBC-2001 FUEL GAS CODE SECS. 401.8 THRU
 402.5.2 & TABLES 402.2(1) THRU 402(34).
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 6. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR PER FBC-2001 FUEL GAS CODE SEC 304.
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 GAS CODE SEC. 402.2. IF
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 8. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2001 FUEL GAS CODE SEC
 502 THRU 506.
 10. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 11. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377