| Plan Review Notes For Permit 02070539 |
| Permit Number |
02070539 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-11-13 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE PROVIDE THE FOLLOWING | | | INFORMATION AND RESUBMIT FOR REVIEW. | | | | | | 1} THE RISER DIAGRAM ONLY SHOWS ONE | | | METER AND PANEL AT THE GARAGE.IS THERE | | | A SEPERATE SERVICE AT THE HOUSE? PLEASE | | | INDICATE COMPLIANCE WITH 250-32(A) & | | | (D) ON THE RISER DIAGRAM. | | | | | | 2} PLEASE SHOW LOAD CALCULATIONS AND | | | PANEL SCHEDULES FOR ALL PANELS PER | | | 215-5 & 220-3(C)(1). | | | | | | 3} THE AHU IN THE CABANA MUST COMPLY | | | WITH 210-63 IF APPLICABLE. | | | | | | 4} PLEASE CLARIFY THE PANEL SCHEDULE | | | NOTES,SEE HI-LIGHTED PORTION. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/659-8096 EXT. 8392 |
|