| Plan Review Notes For Permit 02070459 |
| Permit Number |
02070459 |
|
| Review Stop |
FS |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-07-09 00:00:00 | 1) PLANS INDICATE THE 1996 EDITION OF | | | NFPA 13. THE PLANS SHALL READ 1999 | | | EDITION OF NFPA 13. | | | | | | 2) PLEASE INDICATE ON THE PLANS ANY | | | AREAS THAT WILL NOT BE SPRINKLER | | | PROTECTED THAT IS ALLOWABLE BY CODE. | | | | | | 3) NO PRODUCT APPROVALS PROVIDED FOR | | | FIRE SPRINKLER HEADS OR OTHER | | | EQUIPMENT PLANNED FOR USE. | | | | | | 4) PLEASE INDICATE ON THE PLANS THE | | | LOCATION OF THE SPARE SPRINKLER HEADS | | | AND WRENCH WILL BE STORED. | | | | | | 5) STANDPIPE VALVES ARE TO BE REDUCED | | | FROM 2 1/2 TO 1 1/2. | | | | | | 6) PLANS SHALL INDICATE MINIMUM | | | CLEARANCES TO FIRE PROTECTION DEVICES | | | TO BE AT LEAST SEVEN AND HALF FEET. | | | | | | 7) BACKFLOW DEVICE SHALL HAVE TAMPER | | | SWITCHES, CHAINS AND LOCKS. | | | | | | 8) PLEASE CLEARLY INDICATE ALL RISER | | | CLAMPS FOR STANDPIPE SYSTEM. | | | | | | 9) PLEASE PROVIDE ELEVATION DRAWINGS | | | FOR ALL VERTICAL SHAFTS. NO DETAILS | | | FOR EXAMPLE PROVIDED FOR FIRE | | | SPRINKLER PROTECTION FOR THE TRASH | | | CHUTE. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|