Plan Review Notes
Plan Review Notes For Permit 02070448
Permit Number 02070448
Review Stop E
Sequence Number 1
Notes
Date Text
2002-07-29 00:00:00FAILED
 ~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 ON THE PLANS AND RESUBMIT FOR REVIEW.
  
 1} SMOKE DETECTOR IN THE BATHROOM IS IN
 VIOLATION OF 2-5.2.1.6(B),NFPA-72.
  
 2} THE GROUND BETWEEN THE PANEL AND THE
 MAIN DISCONNECT IS IN VIOLATION OF
 250-6(B)(1).
  
  
 THERE ARE NO SMALL APPLIANCE CIRCUITS IN
 THE LOAD CALCS OR ON THE PANEL SCHEDULE
 AS REQUIRED BY 220-16(A).
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392