| Plan Review Notes For Permit 02070448 |
| Permit Number |
02070448 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-07-29 00:00:00 | FAILED | | | ~~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | ON THE PLANS AND RESUBMIT FOR REVIEW. | | | | | | 1} SMOKE DETECTOR IN THE BATHROOM IS IN | | | VIOLATION OF 2-5.2.1.6(B),NFPA-72. | | | | | | 2} THE GROUND BETWEEN THE PANEL AND THE | | | MAIN DISCONNECT IS IN VIOLATION OF | | | 250-6(B)(1). | | | | | | | | | THERE ARE NO SMALL APPLIANCE CIRCUITS IN | | | THE LOAD CALCS OR ON THE PANEL SCHEDULE | | | AS REQUIRED BY 220-16(A). | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/659-8096 EXT. 8392 |
|