| Notes |
| Date |
Text |
| 2002-07-10 00:00:00 | ~~~~~~~~~~~~~~~~~UNSAT~~~~~~~~~~~~~~~~~~ | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE PROVIDE THE FOLLOWING | | | INFORMATION,MAKE NECESSSARY CHANGES ON | | | THE PLANS AND RESUBMIT FOR REVIEW. | | | | | | 1} PLEASE PROVIDE A LOAD CALCULATION AND | | | SHOW ALL ADDITIONAL PROPOSED LOADS ON | | | SAME. | | | | | | 2} NOTE THAT THE LOCATION OF THE | | | ELECTRIC PANEL WOULD NOT COMPLY WITH | | | ARTICLE 110-26 IF THE WASHER IS PLACED | | | AS SHOWN. | | | | | | 3} PLEASE ADD A SMOKE DETECTOR PER | | | 2-2.1.1.1 NFPA-72,AND INTERCONNECT PER | | | 2-2.2.1. | | | | | | IF THERE ARE ANY QUESTIONS,PLEASE CALL: | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/659-8096 EXT. 8392 |
|