| Plan Review Notes For Permit 02070311 |
| Permit Number |
02070311 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-08-02 00:00:00 | 1) TEMPORARY WALLS SHALL NOT CONSIST | | | OF NON-FIRE RATED VISQUEEN OR OTHER | | | NON-APPROVED MATERIALS. | | | | | | 2) THE TEMPORARY WALLS ARE NOT TO | | | INTERFERE WITH ANY REQUIRED FIRE | | | SPRINKLER SYSTEM PROTECTION. | | | | | | 3) PERMITS REQUIRED FOR ANY NEW | | | FIRE SPRINKLER OR FIRE ALARM WORK. | | | | | | 4) DEBRIS FROM DEMOLITION SHALL BE | | | REMOVED DAILY. | | | | | | 5) THE FIRE SPRINKLER SYSTEM SHALL | | | REMAIN ON DURING CONSTRUCTION. IF | | | PORTIONS OF THE SYSTEM MUST BE TURNED | | | OFF, ALL CODE REQUIREMENTS ARE TO BE | | | FOLLOWED WITH REGARDS TO NOTIFICATION | | | OF FIRE RESCUE, HOSPITAL, AND FIRE | | | ALARM MONITORING COMPANY. FIRE WATCHES | | | MUST IF NECESSARY MUST BE COORDINATED | | | WITH THE BUREAU OF FIRE PREVENTION, | | | 835-2910. | | | | | | 6) PLEASE INDICATE INTERIOR FINISH | | | CLASSIFICATION FOR WALLS AND CEILINGS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|