| 2002-08-02 00:00:00 | *********** UNSAT******************** | | | | | | 1)NOTE: PLEASE CLARIFY SECOND PANEL AND | | | METER? SHOWN ON BLDG LAYOUT. SECOND | | | PANEL ON INTERIOR? | | | | | | 2)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS | | | AT 125%. PLEASE NOTE THAT AT THIS | | | LOCATION MANY LOADS WILL SEE 3 OR MORE | | | HOURS. | | | | | | 3)NOTE: PLEASE SUBMIT TWO MORE SETS OF | | | PLANS. PLEASE NOTE THAT THESE ARE | | | PERMITTED SEPARATELY AND WILL BE FILED | | | UNDER SEPARATE #`S. SEPARATE ADDRESSES. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW AND IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|