| Plan Review Notes For Permit 02070302 |
| Permit Number |
02070302 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-08-06 00:00:00 | THE CODE DATA SHEET AND SOME PLACES ON | | | THE PLAN DECLARED DESIGN TO THE 1997 | | | SBCCI.THE 2001 FBC IS THE CODE IN | | | EFFECT.PLEASE REVISE AND ENSURE | | | COMPLIANCE AS NECESSARY. | | | | | | THE CENTRAL TOWER INC. SHEETS ARE | | | REQUIRED TO HAVE THE ENGINEER'S | | | EMBOSSED SEAL. | | | THE DESIGN MUST COMPLY WITH THE FBC | | | (ASCE 7-98) FOR WIND LOADS. | | | | | | THERE ARE NO CONSTRUCTION DETAILS FOR | | | THE TOWERS OR THE ANTENNAS TO BE | | | ATTACHED TO THEM.THE INFORMATION IS | | | NECESSARY IF THEY ARE TO BE CONSTRUCTED | | | UNDER THIS PERMIT. | | | | | | SHOW THE RISE RUN DETAILS FOR THE | | | STAIRS. SEE FBC 1007. | | | | | | SHOW THE WIND PRESSURES FOR THE | | | COMPONENTS AND CLADDING. | | | | | | IF THE NOTICE OF ACCEPTANCE OR TEST | | | REPORTS FOR THE WINDOWS, DOORS AND ROOF | | | COVERING ARE NOT INCLUDED WITH THIS | | | PERMIT APPLICATION, SEPARATE PERMITS | | | AND ADDITIONAL FEES WILL BE REQUIRED. |
|