Plan Review Notes
Plan Review Notes For Permit 02070302
Permit Number 02070302
Review Stop B
Sequence Number 1
Notes
Date Text
2002-08-06 00:00:00THE CODE DATA SHEET AND SOME PLACES ON
 THE PLAN DECLARED DESIGN TO THE 1997
 SBCCI.THE 2001 FBC IS THE CODE IN
 EFFECT.PLEASE REVISE AND ENSURE
 COMPLIANCE AS NECESSARY.
  
 THE CENTRAL TOWER INC. SHEETS ARE
 REQUIRED TO HAVE THE ENGINEER'S
 EMBOSSED SEAL.
 THE DESIGN MUST COMPLY WITH THE FBC
 (ASCE 7-98) FOR WIND LOADS.
  
 THERE ARE NO CONSTRUCTION DETAILS FOR
 THE TOWERS OR THE ANTENNAS TO BE
 ATTACHED TO THEM.THE INFORMATION IS
 NECESSARY IF THEY ARE TO BE CONSTRUCTED
 UNDER THIS PERMIT.
  
 SHOW THE RISE RUN DETAILS FOR THE
 STAIRS. SEE FBC 1007.
  
 SHOW THE WIND PRESSURES FOR THE
 COMPONENTS AND CLADDING.
  
 IF THE NOTICE OF ACCEPTANCE OR TEST
 REPORTS FOR THE WINDOWS, DOORS AND ROOF
 COVERING ARE NOT INCLUDED WITH THIS
 PERMIT APPLICATION, SEPARATE PERMITS
 AND ADDITIONAL FEES WILL BE REQUIRED.