Plan Review Notes
Plan Review Notes For Permit 02070266
Permit Number 02070266
Review Stop P
Sequence Number 1
Notes
Date Text
2002-07-20 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 MECHANICAL
  
 1) SHT A2.02 TOILET ROOM #26, 11-4.22.4,
 IF TOILET STALLS ARE PROVIDED, THEN AT
 LEAST ONE STALL SHALL BE A STANDARD
 STALL COMPLYING WITH 11-4.17. (FIG 30A)
 2) SHT P-1 PLEASE CONTACT RODNEY COMPO,
 ENVIRONMENTAL COMPLIANCE MANAGER TO SIZE
 GREASE INTERCEPTOR. SEE ATTACHED SHEET
 FOR APPROVED CITY WEST PALM DETAIL.
 3) PLEASE ROUTE PLANS TO THE PALM BEACH
 COUNTY HEALTH UNIT, DIVISION OF ENVIRON-
 MENTAL HEALTH - 901 EVERNIA WPB (561)
 355-3018 FOR PLAN REVIEW BEFORE RESUB-
 MITTING TO THE CITY FOR PLAN REVIEW.
 4) SHT P-1 SINKS IN FOOD PREP AREA SHALL
 DRAIN INDIRECTLY TO AN APPROVED RECEPTI-
 CAL (FLOOR SINK)
 5) SHTS P-1, P-2, & P-3 SAFE WASTE IS
 NOT APPROVED. ALL INDIRECT WASTE SHALL
 DRAIN INTO A FLOORSINK. SEC 802.3 LOCATE
 ALL FLOOR SINKS UNDER UNITS BEING DRAIN-
 ED. FLOOR DRAINS NOT APPROVED
 6) TABLE 401.3 REQUIRES A DRINKING
 FOUNTAIN. PLEASE SUBMIT DETAIL. SHOW
 COMPLIANCE WITH 11-4.15 AND ALL SUBSECT-
 IONS AND WITH 11-4.1.3(10)(A) PROVISIONS
 FOR THOSE WHO HAVE TROUBLE BENDING OR
 STOOPING.
 7) SHT P-1 DISHWASHER SHALL DRAIN INTO
 SANITARY SYSTEM, NOT GREASE PER UTILITY
 ORD.
 8) SHT P-1 CONDENSORS 23.03/23.04 SHALL
 DRAIN TO FLOOR SINK. 802.3
 9) BACKFLOW REQUIRED ON WATER SERVICE.
 10) SHT P-2 WATER ISOMETRIC, WATER HAM-
 MER ARRESTORS ARE REQUIRED PER 604.9.
 IF USED, THEY SHALL BE LOCATED NEAR FIX-
 TURE IN AN "EFFECTIVE RANGE" NOT AT TOP
 OF DROP AS SHOWN. PDI-WH 201 & MANUFACT-
 URE INSTALLATION INSTRUCTIONS.
 11) SHT P-2 WATER HEATER NOT SHOWN ON
 WATER ISOMETRIC. SHOW DETAIL FOR PIPING
 OF PAN DRAIN AND RELIEV VALVE (T/P) DIS-
 CHARGE PIPING. COMPLY WITH SECTIONS
 504.7 AND 607.3.2 - SHOW ON WATER HEATER
 DETAIL.
 12) SHT P-3 FLOOR DRAIN - SAFE WASTE
 DETAIL NOT APPROVED. DELETE DETAIL
 13) SHT P-2 GAS ISOMETRIC, SALAMANDER
 NOT SHOWN ON SHT A6.01 KITCHEN KEY PLAN
 & DETAILS.
 14) GAS PERMIT REQUIREMENTS. INFORMATION
 REQUIRED FOR GAS PERMIT.
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 B. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODESEC 402.2 IF
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 C. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND FBC-2001
 FUEL GAS CODE SEC. 402.2
 D. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. NO HOOD
 SHUT DOWN SHOWN ON PLANS.
 15) PLEASE PROVIDE CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS PER
 SECS. 1106 & 1107. ADD 1/2 AREA OF ALL
 VERTICAL WALLS AND AREA OF ROOFS DRAIN-I
 ING FROM ABOVE. SHOW LOCATION OF ALL
 DRAINS ON PLANS.
 16) SHT P-3 MATERIALS AND EQUIPMENT "L"
 AND EXECUTION OF WORK "F" AIR CHAMBERS
 ARE NOT APPROVED. PLEASE DELETE REFEREN-
 CE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved