| Date |
Text |
| 2002-07-20 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 CHAPTER 11 |
| | FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 MECHANICAL |
| | |
| | 1) SHT A2.02 TOILET ROOM #26, 11-4.22.4, |
| | IF TOILET STALLS ARE PROVIDED, THEN AT |
| | LEAST ONE STALL SHALL BE A STANDARD |
| | STALL COMPLYING WITH 11-4.17. (FIG 30A) |
| | 2) SHT P-1 PLEASE CONTACT RODNEY COMPO, |
| | ENVIRONMENTAL COMPLIANCE MANAGER TO SIZE |
| | GREASE INTERCEPTOR. SEE ATTACHED SHEET |
| | FOR APPROVED CITY WEST PALM DETAIL. |
| | 3) PLEASE ROUTE PLANS TO THE PALM BEACH |
| | COUNTY HEALTH UNIT, DIVISION OF ENVIRON- |
| | MENTAL HEALTH - 901 EVERNIA WPB (561) |
| | 355-3018 FOR PLAN REVIEW BEFORE RESUB- |
| | MITTING TO THE CITY FOR PLAN REVIEW. |
| | 4) SHT P-1 SINKS IN FOOD PREP AREA SHALL |
| | DRAIN INDIRECTLY TO AN APPROVED RECEPTI- |
| | CAL (FLOOR SINK) |
| | 5) SHTS P-1, P-2, & P-3 SAFE WASTE IS |
| | NOT APPROVED. ALL INDIRECT WASTE SHALL |
| | DRAIN INTO A FLOORSINK. SEC 802.3 LOCATE |
| | ALL FLOOR SINKS UNDER UNITS BEING DRAIN- |
| | ED. FLOOR DRAINS NOT APPROVED |
| | 6) TABLE 401.3 REQUIRES A DRINKING |
| | FOUNTAIN. PLEASE SUBMIT DETAIL. SHOW |
| | COMPLIANCE WITH 11-4.15 AND ALL SUBSECT- |
| | IONS AND WITH 11-4.1.3(10)(A) PROVISIONS |
| | FOR THOSE WHO HAVE TROUBLE BENDING OR |
| | STOOPING. |
| | 7) SHT P-1 DISHWASHER SHALL DRAIN INTO |
| | SANITARY SYSTEM, NOT GREASE PER UTILITY |
| | ORD. |
| | 8) SHT P-1 CONDENSORS 23.03/23.04 SHALL |
| | DRAIN TO FLOOR SINK. 802.3 |
| | 9) BACKFLOW REQUIRED ON WATER SERVICE. |
| | 10) SHT P-2 WATER ISOMETRIC, WATER HAM- |
| | MER ARRESTORS ARE REQUIRED PER 604.9. |
| | IF USED, THEY SHALL BE LOCATED NEAR FIX- |
| | TURE IN AN "EFFECTIVE RANGE" NOT AT TOP |
| | OF DROP AS SHOWN. PDI-WH 201 & MANUFACT- |
| | URE INSTALLATION INSTRUCTIONS. |
| | 11) SHT P-2 WATER HEATER NOT SHOWN ON |
| | WATER ISOMETRIC. SHOW DETAIL FOR PIPING |
| | OF PAN DRAIN AND RELIEV VALVE (T/P) DIS- |
| | CHARGE PIPING. COMPLY WITH SECTIONS |
| | 504.7 AND 607.3.2 - SHOW ON WATER HEATER |
| | DETAIL. |
| | 12) SHT P-3 FLOOR DRAIN - SAFE WASTE |
| | DETAIL NOT APPROVED. DELETE DETAIL |
| | 13) SHT P-2 GAS ISOMETRIC, SALAMANDER |
| | NOT SHOWN ON SHT A6.01 KITCHEN KEY PLAN |
| | & DETAILS. |
| | 14) GAS PERMIT REQUIREMENTS. INFORMATION |
| | REQUIRED FOR GAS PERMIT. |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | FUEL GAS CODE. |
| | B. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2001 FUEL GAS CODESEC 402.2 IF |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | C. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND FBC-2001 |
| | FUEL GAS CODE SEC. 402.2 |
| | D. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. NO HOOD |
| | SHUT DOWN SHOWN ON PLANS. |
| | 15) PLEASE PROVIDE CALCULATIONS FOR |
| | PRIMARY AND SECONDARY ROOF DRAINS PER |
| | SECS. 1106 & 1107. ADD 1/2 AREA OF ALL |
| | VERTICAL WALLS AND AREA OF ROOFS DRAIN-I |
| | ING FROM ABOVE. SHOW LOCATION OF ALL |
| | DRAINS ON PLANS. |
| | 16) SHT P-3 MATERIALS AND EQUIPMENT "L" |
| | AND EXECUTION OF WORK "F" AIR CHAMBERS |
| | ARE NOT APPROVED. PLEASE DELETE REFEREN- |
| | CE. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 659-8096 EXT 8377 |