| 2002-08-02 00:00:00 | 1) NUMERICAL ADDRESS REQUIRED ON |
| | BUILDING. |
| | |
| | 2) SEPARATE PLANS AND PERMITS REQUIRED |
| | FOR HOOD, DUCT, AND FIRE SUPPRESSION |
| | SYSTEM. |
| | |
| | 3) ALL CORRIDORS SHALL PROVIDE A |
| | MINIMUM OF AT LEAST FORTY FOUR INCHES |
| | IN CLEAR WIDTH. SEVERAL LOCATIONS ON |
| | THE PLANS DO NOT MEET THIS MINIMUM |
| | CODE REQUIREMENT. |
| | |
| | 4) IF THE BUILDING IS NOT FIRE |
| | SPRINKLER PROTECTED, ALL ELECTRICAL, |
| | MECHANICAL, AND STORAGE ROOMS ARE |
| | REQUIRED TO BE AT LEAST ONE HOUR |
| | FIRE RATED WITH AT LEAST FORTY FIVE |
| | MINUTE FIRE RATED FIRE DOORS. PLEASE |
| | REVISE PLANS TO REFLECT THIS. |
| | |
| | 5) SEPARATE PLANS AND PERMITS REQUIRED |
| | FOR ANY FIRE ALARM SYSTEM MODIFICATIONS. |
| | |
| | 6) PLEASE PROVIDE PRODUCT APPROVALS FOR |
| | 3M FIREWRAP IDENTIFIED IN THE PLANS. |
| | THIS INFORMATION CAN BE SUBMITTED NOW |
| | OR WITH THE HOOD PLANS AND PERMIT. |
| | |
| | 7) DRY CHEMICAL FIRE SUPPRESSION SYSTEM |
| | IS NOT PERMITTED. ONLY A WET FIRE |
| | SUPPRESSION SYSTEM WILL BE ALLOWED |
| | SINCE IT MEETS THE UL 300 STANDARD AND |
| | DRY CHEMICAL DOES NOT. PLEASE REVISE |
| | PLANS AS NECESSARY. |
| | |
| | 8) SECURITY DEVICES SHALL NOT INTERFERE |
| | WITH FREE EGRESS FROM THE BUILDING. |
| | |
| | MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| | 659-8096,EXT.8497 |