Plan Review Notes
Plan Review Notes For Permit 02070266
Permit Number 02070266
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2002-08-02 00:00:001) NUMERICAL ADDRESS REQUIRED ON
 BUILDING.
  
 2) SEPARATE PLANS AND PERMITS REQUIRED
 FOR HOOD, DUCT, AND FIRE SUPPRESSION
 SYSTEM.
  
 3) ALL CORRIDORS SHALL PROVIDE A
 MINIMUM OF AT LEAST FORTY FOUR INCHES
 IN CLEAR WIDTH. SEVERAL LOCATIONS ON
 THE PLANS DO NOT MEET THIS MINIMUM
 CODE REQUIREMENT.
  
 4) IF THE BUILDING IS NOT FIRE
 SPRINKLER PROTECTED, ALL ELECTRICAL,
 MECHANICAL, AND STORAGE ROOMS ARE
 REQUIRED TO BE AT LEAST ONE HOUR
 FIRE RATED WITH AT LEAST FORTY FIVE
 MINUTE FIRE RATED FIRE DOORS. PLEASE
 REVISE PLANS TO REFLECT THIS.
  
 5) SEPARATE PLANS AND PERMITS REQUIRED
 FOR ANY FIRE ALARM SYSTEM MODIFICATIONS.
  
 6) PLEASE PROVIDE PRODUCT APPROVALS FOR
 3M FIREWRAP IDENTIFIED IN THE PLANS.
 THIS INFORMATION CAN BE SUBMITTED NOW
 OR WITH THE HOOD PLANS AND PERMIT.
  
 7) DRY CHEMICAL FIRE SUPPRESSION SYSTEM
 IS NOT PERMITTED. ONLY A WET FIRE
 SUPPRESSION SYSTEM WILL BE ALLOWED
 SINCE IT MEETS THE UL 300 STANDARD AND
 DRY CHEMICAL DOES NOT. PLEASE REVISE
 PLANS AS NECESSARY.
  
 8) SECURITY DEVICES SHALL NOT INTERFERE
 WITH FREE EGRESS FROM THE BUILDING.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910