Plan Review Notes
Plan Review Notes For Permit 02070262
Permit Number 02070262
Review Stop B
Sequence Number 1
Notes
Date Text
2002-07-31 00:00:001. PLANS REVIEWED BY BUILDING
 OFFICIAL AT REQUEST OF M. E. SHEKMER
 JR. PE, REQUESTING APPLICATION OF FBC,
 3401.4.
 2. PROVIDE DETAIL AS TO CONDITION OF
 PIPE COLUMS AND LOCATION WHERE NEW
 SECTION IS TO BE ADDED.
 3. PROVIDE CERTIFICATE FOR CERTIFIED
 WELDER PERFORMING THE WORK.
 4. PROVIDE DETAILS ON HOW CANOPY IS TO
 BE ATTACHED TO THE EXISTING STRUCTURE
 AND CERTIFY THAT THE STRUCTURE CAN
 RECEIVE THE NEW LOADS AS IMPOSED.
 5. ENGINEER OF RECORD TO INSPECT WELDING
 BY CERTIFED WELDER MEET MINUMIN
 SPECIFICATIONS FOR WELDING, FBC CHAPTER
 22 SECTION 2207.