2002-07-26 00:00:00PROVISO:MECHANICAL PERMIT 02070353
  
 MANUAL J CALCULATIONS DO NOT MATCH
 ENERGY CACLS OR EQUIPMENT SPECIFIED ON
 PLAN.PLEASE NOTE THE ADDRESS ON PAGE
 2 OF THE ENERGY CALCS & MANUAL JDO
 NOT CORRELATE (9277 ON PG 1 OF ENERGY
 CALCS & 9227 IS INDICATED ON PAGE 2 &
 ON THE MANUAL J).
  
 PLEASE SUBMIT CORRECT MANUAL J.
  
 SMOKE DETECTORS SHALL BE INSTALLED
 SUPPLY SYSTEMS WITH A DESIGN CAPACITY
 GREATER THAN 2,000 CFM, IN THE SUPPLY
 AIR DUCT. 2001 FBC(M) 606.2.1OR
 UPON ACTIVATION, THE SMOKE DETECTORS
 SHALL SHUTDOWN THE AIR DISTRIBUTION
 SYSTEM. 2001 FBC(M) 606.4
  