| Plan Review Notes For Permit 02070257 |
| Permit Number |
02070257 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-07-26 00:00:00 | PROVISO:MECHANICAL PERMIT 02070353 | | | | | | MANUAL J CALCULATIONS DO NOT MATCH | | | ENERGY CACLS OR EQUIPMENT SPECIFIED ON | | | PLAN.PLEASE NOTE THE ADDRESS ON PAGE | | | 2 OF THE ENERGY CALCS & MANUAL JDO | | | NOT CORRELATE (9277 ON PG 1 OF ENERGY | | | CALCS & 9227 IS INDICATED ON PAGE 2 & | | | ON THE MANUAL J). | | | | | | PLEASE SUBMIT CORRECT MANUAL J. | | | | | | SMOKE DETECTORS SHALL BE INSTALLED | | | SUPPLY SYSTEMS WITH A DESIGN CAPACITY | | | GREATER THAN 2,000 CFM, IN THE SUPPLY | | | AIR DUCT. 2001 FBC(M) 606.2.1OR | | | UPON ACTIVATION, THE SMOKE DETECTORS | | | SHALL SHUTDOWN THE AIR DISTRIBUTION | | | SYSTEM. 2001 FBC(M) 606.4 | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|