| Plan Review Notes For Permit 02070030 |
| Permit Number |
02070030 |
|
| Review Stop |
R |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2002-11-13 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1-SEE ENGINEERING ANALYSIS AND REVISE | | | DIAPHRAGM SCHEDULE AND WALL SECTIONS/ | | | DETAILS SPECS REGARDING SIZE OF FASTE- | | | NERS. | | | 2-CLARIFY SIZE OF FOOTINGS SHOWN ON THE | | | FOOTING SCHEDULE. WIDTH AND LENGTH ARE | | | REVERSED. SEE SCHEDULE AND DETAILS. | | | 3-PROVIDE PRODUCT APPROVAL FOR SIDE DOOR | | | AT GARAGE. | | | 4-STORM SHUTTERS: A)DESOGN PRESSURES | | | SPECIFIED ON THE INSTALLATION SCHEDULE | | | HAVE LIMITATIONS ON THE PANEL SPAN. | | | SEE DESIGN PRESSURES CALCULATED BY THE | | | ARCHITECT AND REVISE ACCORDINGLY. | | | ALSO, CLARIFY TYPE OF ANCHOR USED RAWL | | | OR CAULK-IN. | | | B)MARK ON DRAWINGS SPECIFIC MOUNTING | | | CONDITIONS AND ANCHOR TYPE AND SPACING | | | TO BE USED. |
|