| Plan Review Notes For Permit 02061904 |
| Permit Number |
02061904 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-07-16 00:00:00 | 1) WET FIRE HYDRANTS REQUIRED PRIOR TO, | | | DURING AND AFTER CONSTRUCTION. | | | | | | 2) SECURITY GATES NOTED ON GEOMETRIC | | | SITE PLAN ARE NOT WIDE ENOUGH. MINIMUM | | | WIDTH SHALL BE AT LEAST TWENTY FEET (20) | | | FEET IN CLEAR WIDTH. | | | | | | 3) WHAT PROVISIONS HAVE BEEN MADE FOR | | | FIRE AND PARAMEDICAL ACCESS THRU THE | | | SECURITY FEATURES. | | | | | | 4) TRAVEL LANES SHOWN BETWEEN EXISTING | | | MEDICAL OFFICE BUILDING AND FUTURE | | | OFFICE BUILDING DISPLAYS ONLY TWELVE | | | (12) FEET. SEE PAGES C7AND C8. | | | | | | 5) PLEASE INDICATE ANY AND ALL | | | DESIGNATED FIRE LANES TO ALL NEW | | | PROPOSED BUILDINGS. | | | | | | 6) NO DETAILS ON HOW FIRE LANES WILL | | | BE IDENTIFIED. | | | | | | 7) PROPOSED WORK IS NOT TO INTEFERE | | | WITH FIRE RESCUE ACCESS TO THE EXISTING | | | EMERGENCY ROOM. | | | | | | 8) NO CONSTRUCTION FENCING IS TO | | | INTERFERE WITH ANY EXISTING EXIT | | | DISCHARGE OR EXISTING FIRE HYDRANTS. | | | | | | 9) TAMPER SWITCHES, CHAINS AND LOCKS | | | ARE REQUIRED ON FIRE LINE BACKFLOW | | | DEVICES. | | | | | | 10) ADDITIONAL FIRE HYDRANTS APPEAR TO | | | BE NEEDED NEAR THE NEW BUILDINGS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|