Plan Review Notes
Plan Review Notes For Permit 02061904
Permit Number 02061904
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2002-07-16 00:00:001) WET FIRE HYDRANTS REQUIRED PRIOR TO,
 DURING AND AFTER CONSTRUCTION.
  
 2) SECURITY GATES NOTED ON GEOMETRIC
 SITE PLAN ARE NOT WIDE ENOUGH. MINIMUM
 WIDTH SHALL BE AT LEAST TWENTY FEET (20)
 FEET IN CLEAR WIDTH.
  
 3) WHAT PROVISIONS HAVE BEEN MADE FOR
 FIRE AND PARAMEDICAL ACCESS THRU THE
 SECURITY FEATURES.
  
 4) TRAVEL LANES SHOWN BETWEEN EXISTING
 MEDICAL OFFICE BUILDING AND FUTURE
 OFFICE BUILDING DISPLAYS ONLY TWELVE
 (12) FEET. SEE PAGES C7AND C8.
  
 5) PLEASE INDICATE ANY AND ALL
 DESIGNATED FIRE LANES TO ALL NEW
 PROPOSED BUILDINGS.
  
 6) NO DETAILS ON HOW FIRE LANES WILL
 BE IDENTIFIED.
  
 7) PROPOSED WORK IS NOT TO INTEFERE
 WITH FIRE RESCUE ACCESS TO THE EXISTING
 EMERGENCY ROOM.
  
 8) NO CONSTRUCTION FENCING IS TO
 INTERFERE WITH ANY EXISTING EXIT
 DISCHARGE OR EXISTING FIRE HYDRANTS.
  
 9) TAMPER SWITCHES, CHAINS AND LOCKS
 ARE REQUIRED ON FIRE LINE BACKFLOW
 DEVICES.
  
 10) ADDITIONAL FIRE HYDRANTS APPEAR TO
 BE NEEDED NEAR THE NEW BUILDINGS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910