| Plan Review Notes For Permit 02061893 |
| Permit Number |
02061893 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-07-22 00:00:00 | *******************DENIED*************** | | | | | | 2001 FBC(M) 402.2 - NATURAL VENTILATION | | | FOR OUTSIDE AIR REQUIRMENT. SHOW | | | COMPLIANCE FOR THE MINIMUM OPENABLE AREA | | | TO THE OUTDOORS. (4 PERCENT OF THE FLOOR | | | AREA BEING VENTILATED) OR TABLE 403.3 | | | FOR MECHANICAL VENTILATION. | | | | | | PLEASE INDICATE SIZE OF DUCT & GRILLES | | | FOR THE R/A. | | | | | | PROVIDE ENERGY & MANUAL J CALCS IN | | | ACCORDANCE WITH 2001 FBC CHAPTER 13. | | | | | | PLEASE NOTE ATTIC ACCESS FOR THE AHU | | | SHALL BE A MINIMUM OF 30" X 22" (2001 | | | FBC(M) 306.2).THE SERVICE PANEL SHALL | | | BE WITHIN 6 FT OF AN ATTIC ACCESS (2001 | | | FBC CHAPTER 13, 610.ABC.3.5.2) | | | | | | CONDENSATE SHALL DISCHARGE A MINIMUM OF | | | 12" AWAY FROM THE BUILDING STRUCTURE AS | | | PER 2001 FBC 1503.4.4. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|