2002-07-22 00:00:00*******************DENIED***************
  
 2001 FBC(M) 402.2 - NATURAL VENTILATION
 FOR OUTSIDE AIR REQUIRMENT. SHOW
 COMPLIANCE FOR THE MINIMUM OPENABLE AREA
 TO THE OUTDOORS. (4 PERCENT OF THE FLOOR
 AREA BEING VENTILATED) OR TABLE 403.3
 FOR MECHANICAL VENTILATION.
  
 PLEASE INDICATE SIZE OF DUCT & GRILLES
 FOR THE R/A.
  
 PROVIDE ENERGY & MANUAL J CALCS IN
 ACCORDANCE WITH 2001 FBC CHAPTER 13.
  
 PLEASE NOTE ATTIC ACCESS FOR THE AHU
 SHALL BE A MINIMUM OF 30" X 22" (2001
 FBC(M) 306.2).THE SERVICE PANEL SHALL
 BE WITHIN 6 FT OF AN ATTIC ACCESS (2001
 FBC CHAPTER 13, 610.ABC.3.5.2)
  
 CONDENSATE SHALL DISCHARGE A MINIMUM OF
 12" AWAY FROM THE BUILDING STRUCTURE AS
 PER 2001 FBC 1503.4.4.
  