| 2002-07-24 00:00:00 | ******************** UNSAT ************ |
| | |
| | 1)NOTE: PLEASE NOTE RISER DIAGRAM SHOWS |
| | MCB AND PANEL IS SHOWN AS MLO? PLEASE |
| | CORRLEATE. |
| | |
| | 2) NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ALSO ON EACH LEVEL OF A MULTI-LEVEL |
| | DWELLING UNIT. ROOMS WITH BATHS AND OR |
| | CLOSETS ARE CONSIDERED SLEEPING ROOMS. |
| | PER NFPA-72 2-2.1.1.1. |
| | IN THE VICINITY OF BEDROOMS AND CLOSE |
| | PROXIMITY OF STIRWAYS. 2-5.2.1.3 |
| | 3'FT FROM BATHS/KITCHENS.2-5.2.1.6 |
| | |
| | 3) NOTE: PLEASE SHOW ALL OUTLET SPACING |
| | TO MEET 2`,6`,12` RULE PER 210-52. |
| | MISSING IN SOME LOCATIONS, PLEASE ALSO |
| | NOTE ALMOST THE ENTIRE HOUSE SHOWN AS |
| | BEING REWIRED, PLEASE CLARIFY LIVING RM |
| | AND DINING RM? WHAT WORK IS BEING DONE, |
| | NEW WIRING? EXISTING THAT MEETS 99 NEC |
| | ALREADY? |
| | |
| | 4)) NOTE: PLEASE NOTE FRONT AND REAR |
| | RECEPTS REQ`D PER 210-52E |
| | MISSING FRONT. |
| | |
| | 5))NOTE: PLEASE NOTE, EITHERMISSING |
| | LIGHTING AND/OR CLARIFY EGRESS LIGHTING |
| | PER 210-70 OF THE NEC. |
| | PLEASE NOTE HALLWAY MASTER BED RM AND |
| | FOYER/EXIT TO OUTSIDE. FIXTURE REQ`D |
| | |
| | 6)NOTE: PLEASE PROVIDE ROOM DESIGNATIONS |
| | ON ELECTRICAL PLANS. |
| | |
| | 7 )NOTE: PLEASE LIST THE REQ`D ARC |
| | FAULT PROTECTED CIRCUITS ON PANEL |
| | SCHEDULE OR NOTE ON PLANS FOR BRANCH |
| | CIRCUIT PROTECTION. PER 210-12 |
| | ENTIRE BRANCH CIRCUIT IS REQ`D TO HAVE |
| | ARC FAULT PROTECTION. |
| | |
| | 8)NOTE: PLEASE NOTE KITCHEN COUNTERTOP |
| | SPACING OF OUTLETS TO MEET 210-52 (C), |
| | 1,2,3,4,5. |
| | |
| | 9)NOTE: PLEASE NOTE ALL OUTLETS SERVING |
| | KITCHEN COUNTERSPACE ARE TO BE SHOWN AS |
| | GFI/GFI PROTECTED. PER 210-8-A-6 |
| | |
| | 10)NOTE: PLEASE NOTE OCP FOR "GAS" WATER |
| | HEATER SHOWN AS EXCEEDING THE MAX OF |
| | 150% OF LOAD. LOAD FOR GS WATER HEATER |
| | SHOWN AT 2KW? PLEASE VERFIY. 422-11E |
| | |
| | 11)NOTE: PLEASE NOTE OCP/WIRE/LOAD FOR |
| | AHU #1 PLEASE NOTE MIN SIZING PER 424-3 |
| | (B). 125%.MIN. |
| | |
| | 12)NOTE: PLEASE ALSO NOTE OCP SHOWN AS |
| | 2P30 FOR 2KW OF POOL HEATER 422-1 |
| | |
| | 13)NOTE: PLEASE NOTE THAT ONLY ONE SMALL |
| | APPLIANCE CIRCUIT IS SHOWN ON LOAD |
| | CALCULATIONSAND PANEL SCHEDULE. |
| | PLEASE SEE 210-52B,210-11-C-1 TWO MIN. |
| | |
| | 14)NOTE: PLEASE JUST NOTE;PLAN NOTES |
| | MENTION ALL WIRE SMALLER THAN #10 AWG |
| | SHALL BE SOLID. PLEASE NOTE IF THIS IS |
| | NOTED, NO STRANDED WILL BE PERMITTED TO |
| | BE INSTALLED. PLEASE VERIFY |
| | MAY ONLY BE CHANGED BY ARCH OF RECORD. |
| | |
| | 15)NOTE: PLEASE NOTE, PLAN NOTES MENTION |
| | "STANDARD BLDG CODE" PLEASE NOTE WE |
| | ARE UNDER THE "FL BLDG CODE" |
| | |
| | 16)NOTE: PLEASE NOTE MISSING HALLWAY |
| | OUTLET(S) PER 210-52H |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW AND IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |