Plan Review Notes
Plan Review Notes For Permit 02061893
Permit Number 02061893
Review Stop E
Sequence Number 1
Notes
Date Text
2002-07-24 00:00:00******************** UNSAT ************
  
 1)NOTE: PLEASE NOTE RISER DIAGRAM SHOWS
 MCB AND PANEL IS SHOWN AS MLO? PLEASE
 CORRLEATE.
  
 2) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
 IN THE VICINITY OF BEDROOMS AND CLOSE
 PROXIMITY OF STIRWAYS. 2-5.2.1.3
 3'FT FROM BATHS/KITCHENS.2-5.2.1.6
  
 3) NOTE: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
 MISSING IN SOME LOCATIONS, PLEASE ALSO
 NOTE ALMOST THE ENTIRE HOUSE SHOWN AS
 BEING REWIRED, PLEASE CLARIFY LIVING RM
 AND DINING RM? WHAT WORK IS BEING DONE,
 NEW WIRING? EXISTING THAT MEETS 99 NEC
 ALREADY?
  
 4)) NOTE: PLEASE NOTE FRONT AND REAR
 RECEPTS REQ`D PER 210-52E
 MISSING FRONT.
  
 5))NOTE: PLEASE NOTE, EITHERMISSING
 LIGHTING AND/OR CLARIFY EGRESS LIGHTING
 PER 210-70 OF THE NEC.
 PLEASE NOTE HALLWAY MASTER BED RM AND
 FOYER/EXIT TO OUTSIDE. FIXTURE REQ`D
  
 6)NOTE: PLEASE PROVIDE ROOM DESIGNATIONS
 ON ELECTRICAL PLANS.
  
 7 )NOTE: PLEASE LIST THE REQ`D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12
 ENTIRE BRANCH CIRCUIT IS REQ`D TO HAVE
 ARC FAULT PROTECTION.
  
 8)NOTE: PLEASE NOTE KITCHEN COUNTERTOP
 SPACING OF OUTLETS TO MEET 210-52 (C),
 1,2,3,4,5.
  
 9)NOTE: PLEASE NOTE ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE ARE TO BE SHOWN AS
 GFI/GFI PROTECTED. PER 210-8-A-6
  
 10)NOTE: PLEASE NOTE OCP FOR "GAS" WATER
 HEATER SHOWN AS EXCEEDING THE MAX OF
 150% OF LOAD. LOAD FOR GS WATER HEATER
 SHOWN AT 2KW? PLEASE VERFIY. 422-11E
  
 11)NOTE: PLEASE NOTE OCP/WIRE/LOAD FOR
 AHU #1 PLEASE NOTE MIN SIZING PER 424-3
 (B). 125%.MIN.
  
 12)NOTE: PLEASE ALSO NOTE OCP SHOWN AS
 2P30 FOR 2KW OF POOL HEATER 422-1
  
 13)NOTE: PLEASE NOTE THAT ONLY ONE SMALL
 APPLIANCE CIRCUIT IS SHOWN ON LOAD
 CALCULATIONSAND PANEL SCHEDULE.
 PLEASE SEE 210-52B,210-11-C-1 TWO MIN.
  
 14)NOTE: PLEASE JUST NOTE;PLAN NOTES
 MENTION ALL WIRE SMALLER THAN #10 AWG
 SHALL BE SOLID. PLEASE NOTE IF THIS IS
 NOTED, NO STRANDED WILL BE PERMITTED TO
 BE INSTALLED. PLEASE VERIFY
 MAY ONLY BE CHANGED BY ARCH OF RECORD.
  
 15)NOTE: PLEASE NOTE, PLAN NOTES MENTION
 "STANDARD BLDG CODE" PLEASE NOTE WE
 ARE UNDER THE "FL BLDG CODE"
  
 16)NOTE: PLEASE NOTE MISSING HALLWAY
 OUTLET(S) PER 210-52H
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW AND IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372