| Date |
Text |
| 2003-04-03 00:00:00 | **************** UNSAT *************** |
| | |
| | 1)NOTE: PLEASE CORRELATE PLANS, RISER |
| | AND PANEL SCHEDULE. NOTES, MENTION 200A |
| | PANEL W/ 200A MCB AND THE REST SHOW 150A |
| | ??? |
| | |
| | 2)NOTE: PLAN SHOWS WHAT APPEARS TO BE |
| | A METER/MAIN COMBO AND RISER SHOWS A |
| | SEPARATE DISC? |
| | |
| | 3)NOTE: PLEASE LIST THE REQ`D DEDICATED |
| | BATH CIRCUIT(S) PER 210-52D/210-11C-3 |
| | |
| | 4)NOTE: PLEASE LIST THE REQ`D ARC FAULT |
| | PROTECTED CIRCUITS PER 210-12 ON PANEL |
| | SCHEDULE. |
| | 5)NOTE: PLEASE SEE NOTES ON PLANS, THEY |
| | MENTION ALL WORK TO BE DONE PER PALM |
| | BEACH COUNTY, PLEASE NOTE, WORK ADDRESS |
| | IS IN CITY OF WEST PALM BEACH. |
| | |
| | 6)NOTE: PLEASE SIZE OCP FOR AHU PER |
| | 424-3. SHOWN AS 50A, MIN FOR 10KW IS |
| | 60A. |
| | |
| | 7)NOTE: PLEASE SEE MISSING RECEPT FOR |
| | PENINSULAR PER 210-52C-1,2,3,ETC. |
| | PLEASE NOTE, ALL OUTLETS SERVING KITCHEN |
| | COUNTERSPACE ARE TO BE GFI/GFI PROTECTED |
| | PER 210-8-A-6, NOT JUST RECEPTS W/IN 6' |
| | OF SINK AS MENTIONED IN ELEC. NOTE #3. |
| | |
| | 8)NOTE: PLEASE SEE MISSING SD AT THE |
| | BOTTOM OF STAIRS REQ`D PER NFPA-72 |
| | 8-1.4.2 |
| | |
| | 9)NOTE: PLEASE SEE MISSING EQUIPMENT |
| | GROUNDING CONDUCTOR BETWEEN MAIN DISC |
| | AND PANEL. SIZE PER 250-122 |
| | |
| | 10)NOTE: CLOSET LTS ARE SHOWN TOO CLOSE |
| | TO CLOTHES/STORAGE RACK PER 410-8 |
| | |
| | PLEASE NOTE, PLANS WERE ORIG BROUGHT IN |
| | FOR MISC STRUCTURE REPAIRS, AND NOW |
| | ARE COMING IN W/ COMPLETE REDO OF P |
| | PLEASE ADJUST VALUE FOR SCOPEOF WORK |
| | NOW BEING DONE. PER 104.6.5 |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |