| | BUILDING PLAN REVIEW |
| | PERMIT: 02061849 |
| | ADD: 3093 BOLLARD RD |
| | CONT: INTELI HOMES |
| | TEL: (561)432-9022 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | *****BUILDING PROVISO***** |
| | |
| | 1) TABLE 600 0 TO 3' FROM PROPERTY LINE, |
| | NO OPENINGS IN ZERO LOT LINE SIDE OF |
| | UNIT, GLASS BLOCK SHALL BE A FULL 1 HR. |
| | RATING, PROVIDE MANUFACTURERERS SPEC ON |
| | GLASS BLOCK BEFORE BUCK INSPECTION. |
| | |
| | 2) PROVIDE STORM PANEL INFORMATION WITH |
| | INSTALLATION SCHEDULE AND KEY PLAN WITH |
| | SPECIFIC ANCHORS AND MOUNTING TO BE USED |
| | FOR ALL NON-IMPACT GLAZING. |
| | FBC 1606.1.4.MISSING SCHEDULE & KEY PLAN |
| | FL BLD CODE 2001 SECTION 103.6, |
| | 1606.1.4, 1707.4 & 3401.7.2.4. |
| | PROCEDURES: 1(B) A COMPLETE INSTALLATION |
| | SCHEDULE SUMMARIZING & IDENTIFYING |
| | OPENING SIZES, STORY HEIGHTS, UNIT MARK |
| | NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM |
| | BAR REINFORCING REQUIREMENTS, WALL PRES- |
| | SURE ZONES, SLAT TYPES, ETC., SHALL BE |
| | SUBMITTED AT TIME OF PERMIT APPLICATION |
| | TO FACILITATE PLAN REVIEW AND PERMIT |
| | ISSUANCE. |
| | |
| | FAILURE TO PRODUCE A KEY PLAN AND ATTACH |
| | MENT SCHEDULE BEFORE BUCK INSPECTION |
| | SHALLRESULT IN REQUIRING A SEPERATE |
| | PERMIT FOR STORM SHUTTERS. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | (561) 659-8096 X 8412 |