| Plan Review Notes For Permit 02061846 |
| Permit Number |
02061846 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-07-01 00:00:00 | PROVISO FROM MASTER PLAN REVIEW 02010564 | | | | | | PROVIDE MANUFACTRES INSTALLATION | | | INSTRUCTIONS FOR THE FIRE DAMPERS SHOWN | | | ON M-2 | | | | | | PROVIDE ACCESS TO FOR BOOSTER FANS | | | PROVIDE FEEDBACK TO DRYER SHOULD BOOSTER | | | FAN FAIL. | | | | | | PER FBC(M) 504.4, EXHAUST SHALL | | | TERMINATE ON THE OUTSIDE OF THE | | | BUILDING AND SHALL BE EQUIPPED WITH A | | | BACKDRAFT DAMPER AND SHALL NOT HAVE A | | | SCREEN INSTALLED AT THE DUCT | | | TERMINATION. |
|