Plan Review Notes
Plan Review Notes For Permit 02061757
Permit Number 02061757
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2002-07-30 00:00:001) PLEASE PROVIDE MORE DETAILS ON FUEL
 TANK PLANNED FOR USE. THIS WOULD
 INCLUDE ANY AND ALL PRODUCT APPROVALS
 AND APPLICABLE LISTINGS FOR IT.
  
 2) PLEASE PROVIDE MORE DETAILS ON
 GENERATOR. AGAIN PRODUCT APPROVALS
 OR SPECIFICATION BOOKS WOULD BE
 HELPFUL.
  
 3) IT WAS NOTED THAT THE FUEL TANK
 WILL BE LOCATED NEAR THE LOADING DOCK.
 IS THE FUEL TANK SUBJECT TO ANY
 MECHANICAL DAMAGE. PLEASE ADVISE.
  
 4) PLANS SHOULD INDICATE DIESEL OR
 OTHER TYPE OF FUEL PLANNED FOR THE TANK.
  
 5) PLEASE INDICATE ADJACENT PROPERTY
 LINES WITH REGARDS TO GENERATOR AND
 FUEL TANK INSTALLATION.
  
 6) THE VENT LINE FOR THE FUEL TANK
 SHALL BE A MINIMUM OF 12 FEET ABOVE THE
 TANK.
  
 7) VARIOUS DRAWINGS SHOULD BE CORRELATED
 INTO ONE DOCUMENT.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910