| Plan Review Notes For Permit 02061757 |
| Permit Number |
02061757 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-07-30 00:00:00 | 1) PLEASE PROVIDE MORE DETAILS ON FUEL | | | TANK PLANNED FOR USE. THIS WOULD | | | INCLUDE ANY AND ALL PRODUCT APPROVALS | | | AND APPLICABLE LISTINGS FOR IT. | | | | | | 2) PLEASE PROVIDE MORE DETAILS ON | | | GENERATOR. AGAIN PRODUCT APPROVALS | | | OR SPECIFICATION BOOKS WOULD BE | | | HELPFUL. | | | | | | 3) IT WAS NOTED THAT THE FUEL TANK | | | WILL BE LOCATED NEAR THE LOADING DOCK. | | | IS THE FUEL TANK SUBJECT TO ANY | | | MECHANICAL DAMAGE. PLEASE ADVISE. | | | | | | 4) PLANS SHOULD INDICATE DIESEL OR | | | OTHER TYPE OF FUEL PLANNED FOR THE TANK. | | | | | | 5) PLEASE INDICATE ADJACENT PROPERTY | | | LINES WITH REGARDS TO GENERATOR AND | | | FUEL TANK INSTALLATION. | | | | | | 6) THE VENT LINE FOR THE FUEL TANK | | | SHALL BE A MINIMUM OF 12 FEET ABOVE THE | | | TANK. | | | | | | 7) VARIOUS DRAWINGS SHOULD BE CORRELATED | | | INTO ONE DOCUMENT. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|