| 2002-07-24 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE PROVIDE THE FOLLOWING | | | INFORMATION,MAKE ANY NECESSARY CHANGES | | | IN THE PLANS AND RESUBMIT FOR REVIEW: | | | | | | 1} INDICATE THE TYPE OF GROUNDING | | | ELECTRODE SYSTEM BEING USED AT THE | | | GENERATOR. | | | | | | 2} INDICATE THE GROUNDING ELECTRODE | | | CONDUCTOR SIZE AND METHOD OF GROUNDING | | | AT THE ATS. | | | | | | 3} DOES THE ATS HAVE A MECHANICAL MEANS | | | OF DISCONNECT? | | | | | | 4} WHERE IS THE GENERATOR DISCONNECTING | | | MEANS LOCATED? | | | | | | 5} PLEASE LIST THE CONDUIT AND WIRE | | | SIZE FROM THE EXISTING TANSFORMER TO | | | THE ATS. | | | | | | 6} PLEASE INDICATE THE CONDUIT AND WIRE | | | SIZE FROM THE ATS TO MDP-1. | | | | | | 7} INDICATE WHERE THE DISCONNECTING | | | MEANS IS FOR THE BUILDING SERVICE. | | | | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/659-8096 EXT.8392 |
|