Plan Review Notes
Plan Review Notes For Permit 02061757
Permit Number 02061757
Review Stop E
Sequence Number 1
Notes
Date Text
2002-07-03 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PROVIDE THE FOLLOWING INFORMATION,MAKE
 NECESSARY CHANGES IN PLAN AND RESUBMIT
 FOR REVIEW.
  
 1} THE SCOPE OF THIS PROJECT REQUIRES AN
 ENGINEERED SET OF DRAWINGS PER 471.025
 FS AND 553-79 FAC.
  
 2} PLEASE PROVIDE A COPY OF THE
 CONTRACTFOR THE PROPOSED PROJECT
 INCLUDING THE COST OF LABOR AND
 MATERIAL PER 104.6.5 CWPB AMMENDMENTS.
  
 3} THE FPL SERVICE TO THE METER IS
 LISTED AS BEING 120/208 VOLT-3
 PHASE.THE GENERATOR INDICATES A 480
 VOLT OUTPUT ,PLEASE CLARIFY.
  
 4} FPL SERVICE IS LISTED AS 3 PHASE,4
 WIRE,BUT WITH 2 SETS OF 3EA 600
 MCM,WHICH WOULD INDICATE SINGLE
 PHASE,OR THREE PHASE WITH NO NEUTRAL.
 PLEASE CLARIFY.
  
 5} PLEASE PROVIDE A LOAD CALCULATION AND
 PANEL SCHEDULE FOR THE NEW PANEL.
  
 6} INDICATE IF THE SERVICE SHOWN IS
 EXISTING OR NEW. IF NEW PLEASE PROVIDE
 AIC RATINGS PER 110-9 AND CALCULATIONS
 PER 215-5.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT.8392