| Plan Review Notes For Permit 02061757 |
| Permit Number |
02061757 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-07-03 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PROVIDE THE FOLLOWING INFORMATION,MAKE | | | NECESSARY CHANGES IN PLAN AND RESUBMIT | | | FOR REVIEW. | | | | | | 1} THE SCOPE OF THIS PROJECT REQUIRES AN | | | ENGINEERED SET OF DRAWINGS PER 471.025 | | | FS AND 553-79 FAC. | | | | | | 2} PLEASE PROVIDE A COPY OF THE | | | CONTRACTFOR THE PROPOSED PROJECT | | | INCLUDING THE COST OF LABOR AND | | | MATERIAL PER 104.6.5 CWPB AMMENDMENTS. | | | | | | 3} THE FPL SERVICE TO THE METER IS | | | LISTED AS BEING 120/208 VOLT-3 | | | PHASE.THE GENERATOR INDICATES A 480 | | | VOLT OUTPUT ,PLEASE CLARIFY. | | | | | | 4} FPL SERVICE IS LISTED AS 3 PHASE,4 | | | WIRE,BUT WITH 2 SETS OF 3EA 600 | | | MCM,WHICH WOULD INDICATE SINGLE | | | PHASE,OR THREE PHASE WITH NO NEUTRAL. | | | PLEASE CLARIFY. | | | | | | 5} PLEASE PROVIDE A LOAD CALCULATION AND | | | PANEL SCHEDULE FOR THE NEW PANEL. | | | | | | 6} INDICATE IF THE SERVICE SHOWN IS | | | EXISTING OR NEW. IF NEW PLEASE PROVIDE | | | AIC RATINGS PER 110-9 AND CALCULATIONS | | | PER 215-5. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561/659-8096 EXT.8392 |
|