Plan Review Notes
Plan Review Notes For Permit 02061460
Permit Number 02061460
Review Stop R
Sequence Number 2
Notes
Date Text
2002-08-29 00:00:00APPROVED WITH PROVISO:
 1-PROVIDE ENGINEERING ANALYSIS/CALCS FOR
 EXTERIOR MASONRY WALL WITH VERTICAL
 REINFORCEMENT AT 8'-0" O.C. TIED TO
 THE SINGLE BOND BEAM TO CHECK FOR
 LATERAL STABILITY (SEC. 2105 FBC 2001)
 AND LATERAL SUPPORT (SEC. 2107 FBC).
 2-PROVIDE COMPLETE DETAILS AND SPECS FOR
 CONSTRUCTION OF GABLE END TRUSSES AT
 FRONT OF ELEVATION SHOWING HOW ARE THE
 GABLE ENDS STRUCTURALLY CONTINUOUS.
 **NOTE: CLARIFY WHY BLOCKING AT FRONT
 GABLE ENDS IS SHOWN ONLY PARTIALLY AND
 NOT ALL THE WAY TO THE ENDS OF GABLE
 ENDS. SEC. 104.2.1.2 CITY AMENDMENTS
 TO FBC 2001.
 3-SHEET S2:A)CONNECTOR RT820 IS NOT DONE
 BY USP. REVISE AS REQUIRED. SEMCO IS
 OUT OF BUSINESS.
 B)REVISE NOMENCLATURE FOR DETAIL A/S-2.3
 THERE IS NOT SHEET S-2.3.
 C)COLUMNS SPECIFIED ON "ELEVATION A"
 DON'T MATCH THOSE SPECIFIED ON THE
 FOUNDATION PLAN. REVISE AS REQUIRED.
 D)WHERE IS SECTION 1/S2? SEE ROOF PLAN.
 4-REVISE ENERGY CALCULATIONS:
 A)UNDER ATTIC AREA TO BE CALCULATED AS
 REQ'D BY SEC. 602.1ABC.1.2 OF CHAPTER
 13 OF FBC 2001.
 B)OWNER/AGENT TO DATE BOTTOM FORM TOO.
 5-PROVIDE COMPLETE/CORRECT INFORMATION
 FOR STORM SHUTTERS UNDER A SEPARATE
 PERMIT. CITY IMPLEMENTATION STANDARD
 FOR HURRICANE MISSILE IMPACT PROTECT'N
 **NOTE: ENGINEER OF PRODUCT APPROVAL
 SUBMITTED REQUIRES ORIGINAL SIGNED AND
 SEALED DRAWINGS. ALSO, LIMITATIONS ON
 THE PRODUCT APPROVAL REPORT REQUIRES
 ADDITIONAL ENGINEERING FOR SPECIFIC
 MOUNTING CONDITIONS. SEE LIMITATIONS
 ON SHEET 4 OF 4.
 **NO KEY PLAN AND INSTALLATION SCHEDULE
 WERE SUBMITTED IN THIS PACKAGE.
 6-PROVIDE STRUCTURAL BUCK DETAIL FOR
 ARCHED WINDOW USING 2X BUCK.
 **NOTE: FRAMING DETAIL FOR ARCHED OPEN'G
 DOESN'T APPLY FOR INSTALLATION OF
 WINDOWS/DOORS BECAUSE BUCK SHOWN DOES
 NOT HAVE THE THICKNESS REQUIRED TO
 SUPPORT THE WINDOW/DOOR.
 **NOTE: NEED DETAIL FOR MASONRY AND WOOD
 INSTALLATION. SEE ELEVATION.
 7-PROVIDE GENERAL SPECIFICATIONS FOR
 FIREBLOCKING AT ALL CONCEALED SPACES
 AS REQUIRED BY SEC. 2305.1.4 FBC 2001.
 8-SEE PRODUCT APPROVAL FOR GARAGE DOOR
 STRUCTURAL BUCK SPECIFICATIONS AND
 REVISE DETAIL AS REQUIRED.
 9-PROVIDE MORE LEGIBLE DRAWINGS FOR
 GARAGE DOORS.
 10-WINDOW E IN BATHROOM #2 IS REQUIRED
 TO HAVE SAFETY GLASS. SEC. 2405.2 FBC
 11-WHERE IS DETAIL A/S2?
 12-UPDATE TRUSS ANCHOR SCHEDULE.
 **NOTE A)NEED 1 3/4" PENETRATION INTO
 THE WOOD MEMBER IF USING 10D NAILS.
 **PROVIDE ENGINEERING CALCULATIONS FOR
 VALUES NOT SHOWN IN USP CATALOGUE.