Plan Review Notes
Plan Review Notes For Permit 02061460
Permit Number 02061460
Review Stop R
Sequence Number 1
Notes
Date Text
2002-08-14 00:00:00BUILDING DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) INDICATE THE APPLICABLE INTERNAL
 PRESSURE COEFFICIENT AND BASIC WIND
 PRESSURE ON THE PLANS AS REQUIRED BY
 FBC 1606.1.7.
  
 3) PLEASE REVISE GENERAL NOTE #6 TO
 REFERENCE THE 2001 FLORIDA PLUMBING CODE
  
 4) GENERAL NOTE #13 ON A-1 IS ILLEGIBLE.
  
 5) THERE IS NO SECTION A ON SHEET A-3 AS
 REFERENCED ON SHEET A-1. SECTION B ON
 A-3 APPEARS TO BE MISLABELED. PLEASE
 CORRECT.
  
 6) PROVIDE SOIL BEARING TEST REPORT PER
 FBC SECT. 1804.2.2. A SIGNED AND SEALED
 COPY TO BE SUBMITTED FOR PUBLIC RECORD.
  
 7) THE WINDOW (E) IN BATHROOM #2 IS
 REQUIRED TO BE SAFETY GLASS PER FBC
 SECT. 2405.2.1 (2).
  
 8) THE FOOTINGS ARE SHOWN AS 18" THICK
 ON A-4 AND 16" THICK ON S-1. PLEASE
 CORRECT.
  
 9) THE STRUCTURAL NOTES ON S-1 INDICATE
 THAT THE FOOTINGS ARE DESIGNED FOR
 ALLOWABLE SOIL BEARING PRESSURE OF
 2000 PSF AND SOIL STATEMENT ON SAME
 SHEET HAS 2500 PSF. PLEASE CLARIFY.
  
 10) NOTE 3 ON S-2 STATES THAT TRUSS
 LOADS WERE CALCULATED BASED ON 97 SBC
 110 MPH WIND VELOCITY. PLEASE CORRECT TO
 2001 FBC 140 MPH WIND VELOCITY.
  
 11) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - SINGLE HUNG WINDOWS (COVER SHEET DOES
 NOT GO WITH THE OTHER PAGES WHICH ARE
 EXPIRED)
 - LARGE ARCH TOP FIXED GLASS WINDOW AT
 REAR ABOVE SLIDING GLASS DOOR.
 - STRUCTURAL MULLIONS (EXPIRED)
  
 12) PROVIDE INSTALLATION SCHEDULE FOR
 STORM PANELS.
  
 13) PROVIDE A DIAPHRAGM NAILING SCHEDULE
 AND IDENTIFY THE ROOF NAILING ZONES PER
 CHAPTER 23 OF CITY AMENDMENTS TO THE
 2001 FBC.
  
 14) FL BLDG 1909.3 (EXEPTION# 2)
 CONCRETE SLABS ON GRADE CONTAINING 6X6/
 W1.4XW1.4 WELDED WIRE REINFORCEMENT
 FABRIC LOCATED IN THE MIDDLE TO THE
 UPPER 1/3RD OF THE SLAB SHALL BE SUP-
 PORTED BY APPROVED MATERIALS OR SUPPORTS
 AT SPACING NOT TO EXCEED 3 FT OR IN
 ACCORDANCE WITH MANUFACTURER'S SPEC.
 PLEASE INDICATE ON THE PLANS THAT WWF
 WILL BE SUPPORTED AS REQUIRED.
  
 15) THE ANCHORS FOR THE TRUSSES SHOWN IN
 SECTIONS 6 AND 7 ON S-2 ARE NOT
 SPECIFIED. HOW ARE THE BOTTOM CORDS OF
 THESE TRUSSES ANCHORED WHERE THEY MEET
 THE MASONRY WALL? ARE THE BEARING POINTS
 OF THESE TRUSSES THE TOP CORD?
  
 16) PLEASE CORRECT NOTE 1 UNDER
 FOUNDATION NOTES ON C-1 TO 6 MIL POLY
 AS REQUIRED BY FBC 1909.2.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202