Plan Review Notes
Plan Review Notes For Permit 02061416
Permit Number 02061416
Review Stop E
Sequence Number 2
Notes
Date Text
2002-08-20 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE NOTE THE FOLLOWING INFORMATION
 WAS NOT CORRECTLY ADDRESSED FROM THE
 LAST REVIEW.
  
 1} PROVIDE A RISER DIAGRAM WITH SIZE AND
 TYPE OF CONDUITS AND CONDUCTORS
 USED,INCLUDING:
 METER,DISCONNECTS,PANELS,ETC,AND A
 COMPLETE LOAD CALCULATION PER 215-15.
  
 2} SHOW THE GROUNDING SYSTEM PER 250-50.
  
 3} PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.THESE MUST BE
 LISTED ON THE PANEL SCHEDULE.
  
 4} PLEASE NOTE KITCHEN COUNTER-
 -SPACE RECEPT SPACING SHALL MEET ART;
 210-52C 1,2,3,4,AND 5.SHOW SAME ON
 DRAWING (LOCATIONS),ALSO COMPLY WITH
 210-8,THIS INCLUDES THE ISLAND.
  
 5} PLEASE NOTE THAT THE EXISTING PANEL
 LOCATION IS IN VIOLATION OF 110-26,AND
 SHOULD BE CORRECTED TO COMPLY AT THIS
 TIME WHILE INSTALLING A NEW SERVICE.
  
 6} PLEASE NOTE THAT PER NFPA-72
 8-1.4.2,SMOKE DETECTORS SHALL NOT BE
 LOCATED WITHIN 3'OF A BATHROOM OR
 KITCHEN DOOR. THE INTENT OF THIS IS TO
 AVOID NUISANCE ALARMS,AND IT MAY BE
 POSSIBLE TO ELIMINATE OR MOVE THE ONE
 DETECTOR SHOWN ON THE PLAN.
  
 IT IS SUGGESTED THAT YOU SPEAK WITH AN
 ELECTRICAL DESIGNER TO ASSIST YOU WITH
 THESE ISSUES.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT.8392