| 2002-08-20 00:00:00 | UNSAT |
| | ~~~~~ |
| | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ |
| | PLEASE NOTE THE FOLLOWING INFORMATION |
| | WAS NOT CORRECTLY ADDRESSED FROM THE |
| | LAST REVIEW. |
| | |
| | 1} PROVIDE A RISER DIAGRAM WITH SIZE AND |
| | TYPE OF CONDUITS AND CONDUCTORS |
| | USED,INCLUDING: |
| | METER,DISCONNECTS,PANELS,ETC,AND A |
| | COMPLETE LOAD CALCULATION PER 215-15. |
| | |
| | 2} SHOW THE GROUNDING SYSTEM PER 250-50. |
| | |
| | 3} PLEASE LIST THE REQ`D BATH(S) |
| | CIRCUIT(S). PER 210-11-C-3 |
| | MUST BE 20A AND #12AWG.THESE MUST BE |
| | LISTED ON THE PANEL SCHEDULE. |
| | |
| | 4} PLEASE NOTE KITCHEN COUNTER- |
| | -SPACE RECEPT SPACING SHALL MEET ART; |
| | 210-52C 1,2,3,4,AND 5.SHOW SAME ON |
| | DRAWING (LOCATIONS),ALSO COMPLY WITH |
| | 210-8,THIS INCLUDES THE ISLAND. |
| | |
| | 5} PLEASE NOTE THAT THE EXISTING PANEL |
| | LOCATION IS IN VIOLATION OF 110-26,AND |
| | SHOULD BE CORRECTED TO COMPLY AT THIS |
| | TIME WHILE INSTALLING A NEW SERVICE. |
| | |
| | 6} PLEASE NOTE THAT PER NFPA-72 |
| | 8-1.4.2,SMOKE DETECTORS SHALL NOT BE |
| | LOCATED WITHIN 3'OF A BATHROOM OR |
| | KITCHEN DOOR. THE INTENT OF THIS IS TO |
| | AVOID NUISANCE ALARMS,AND IT MAY BE |
| | POSSIBLE TO ELIMINATE OR MOVE THE ONE |
| | DETECTOR SHOWN ON THE PLAN. |
| | |
| | IT IS SUGGESTED THAT YOU SPEAK WITH AN |
| | ELECTRICAL DESIGNER TO ASSIST YOU WITH |
| | THESE ISSUES. |
| | |