| Plan Review Notes For Permit 02061416 |
| Permit Number |
02061416 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-07-01 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE PROVIDE THE FOLLOWING | | | INFORMATION AND RESUBMIT FOR REVIEW. | | | | | | 1} SHOW THE LOCATION OF THE RELOCATED | | | SERVICE. | | | | | | 2} PROVIDE A RISER DIAGRAM WITH SIZE AND | | | TYPE OF CONDUITS AND CONDUCTORS USED. | | | ALSO PLEASE SHOW ALL GEAR CONNECTED WITH | | | THE | | | SERVICE,METER,DISCONNECTS,PANELS,ETC | | | | | | 3} SHOW GROUNDING SYSTEM USED PER 250-50 | | | | | | 4} WHERE IS THE"EXISTING"BATH TO BE | | | RELOCATED? PLEASE INDICATE ON DRAWING. | | | | | | 5} PLEASE SUBMIT LOAD CALCAULATION | | | -S.PER 220,215-5. | | | | | | 6} PLEASE LIST THE REQ`D BATH(S) | | | CIRCUIT(S). PER 210-11-C-3 | | | MUST BE 20A AND #12AWG.INDICATE | | | RECEPTACLE LOCATIONS ON PLAN. | | | | | | 7} PLEASE SHOW MEANS OF DISCONNECT | | | FOR A/C EQUIPMENT PER 440-11. | | | | | | 8} PLEASE NOTE KITCHEN COUNTER- | | | -SPACE RECEPT SPACING SHALL MEET ART; | | | 210-52C 1,2,3,4,AND 5. | | | | | | 9} THE ELECTRICAL NOTES SAY THE SMOKE | | | DETECTOR IS TO BE 110 VOLT,PLEASE NOTE | | | THEY MUST ALSO BE BATTERY BACK-UP PER | | | 2-3.1.2 | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561/659-8096 EXT. 8392 |
|