| Plan Review Notes For Permit 02061404 |
| Permit Number |
02061404 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-06-27 00:00:00 | DENIED: | | | | | | COMMENT #6 (PLAN SHEET A-2) EXHASUT FANS | | | FOR BATHROOMS SHALL BE RECIRCULATING. AS | | | PER 2001 FBC(M) 502.1, EXHUAST SHALL | | | DISCHARGE TO THE OUSIDE OF THE BUILDING. | | | | | | AS PER 2001 FBC(M) 401.6, AIR EXHAUST & | | | INTAKE OPENINGS THAT TERMINATE OUTDOORS | | | SHALL BE PROTECTED WITH CORROSION | | | RESISTANT SCREENS, LOUVERS OR GRILLES. | | | | | | CONDENSATE SHALL DISCHARGE A MINIMUM OF | | | 12" AWAY FROM THE BUILDING STRUCTURE AS | | | PER 2001 FBC 1503.4.4. | | | | | | BALANCED RETURN AIR - 2001 FBC(M) 601.4 | | | RETURN AIR SHALL BE EQUAL TO SUPPLY | | | AIR BY MEANS OF AIR TRANSFER OR A RETURN | | | AIR (JUMPER). | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|