Plan Review Notes
Plan Review Notes For Permit 02061404
Permit Number 02061404
Review Stop E
Sequence Number 1
Notes
Date Text
2002-06-26 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 THE PLANS DO NOT INDICATE THE SCOPE OF
 THE ELECTRICAL WORK.
 THE FOLLOWING INFORMATION IS NEEDED FOR
 THE SERVICE;
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} INDICATE THE EQUIPMENT GROUNDING
 CONDUCTOR PER 250-122.(DISCONNECT TO
 PNL).
  
 3} SHOW THE LOCATION OF THE METER AND
 MAIN DISCONNECT ON THE PLAN.
  
 4} NOTE:PANEL "C" IS SHOWN WITH A
 200AMP CIRCUIT BREAKER,IF THIS IS SHOWN
 ON THE APPROVED SET OF PLANS IT MUST BE
 INSTALLED.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392