| Plan Review Notes For Permit 02061404 |
| Permit Number |
02061404 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-06-26 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | THE PLANS DO NOT INDICATE THE SCOPE OF | | | THE ELECTRICAL WORK. | | | THE FOLLOWING INFORMATION IS NEEDED FOR | | | THE SERVICE; | | | | | | 1} PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 2} INDICATE THE EQUIPMENT GROUNDING | | | CONDUCTOR PER 250-122.(DISCONNECT TO | | | PNL). | | | | | | 3} SHOW THE LOCATION OF THE METER AND | | | MAIN DISCONNECT ON THE PLAN. | | | | | | 4} NOTE:PANEL "C" IS SHOWN WITH A | | | 200AMP CIRCUIT BREAKER,IF THIS IS SHOWN | | | ON THE APPROVED SET OF PLANS IT MUST BE | | | INSTALLED. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/659-8096 EXT. 8392 |
|