Plan Review Notes
Plan Review Notes For Permit 02061404
Permit Number 02061404
Review Stop B
Sequence Number 1
Notes
Date Text
2002-07-14 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 02061404
 ADD: 633 33RD ST
 CONT: FALLON CONSTRUCTION CORP
 TEL: (305) 971-8110
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) ENGINEER TO DETERMINE AS TO THE FIRE
 DAMAGE TO THE FLOOR JOIST,CEILING JOIST,
 RAFTERS OR TRUSS ASSEMBLIES. ENGINEER TO
 DESCRIBE THE AMOUNT OF FLOOR JOIST, CEIL
 ING JOIST OR RAFTERS TO BE REPLACED, OR
 IF NEW MATERIALS ARE TO BE SISTERED TO
 FIRE DAMAGED FRAMING MEMBERS, THE SPLICE
 THE AMOUNT OF FASTENERS, SIZE, ETC.
  
 2) THE WRONG FORM IS USED FOR THE ENERGY
 CALCULATIONS, CHAP. 13.101.2.3 RENOVA-
 TIONS, RENOVATED BUILDINGS SHALL, MEET
 THE PRESCRIPTIVE CONTAINED IN METHOD C
 OF SUB-CHAPTER 6 FOR RESIDENTIAL BUILD-
 ING.
 NO INSULATION UNDER WOOD FLOOR?
  
 3) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 THE PLAN DOES NOT INDICATE AS TO WHAT
 THE WALLS ARE CONSTRUCTED OF? WOOD WALLS
 DO THEY MEET THE WIND REQUIREMENTS,
 CONTINIOUS WIND RESTRAINT?
  
 4)FIGURE 1606 WIND-BORNE DEBRIS
 REGION; INDICATES THAT W.P.B. CITY OF IS
 LOCATED IN THE 140 MPH ZONE. PLANS ARE
 TO INDICATE THIS.
  
 5)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 6) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED. MISSING REPORTS:
 A) WINDOW MULLION
 B) ROOFING
  
 7)1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 8)1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 9)FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE. ATTACHED SAMPLE SCHEDULE.
  
 10) 1606.4.4 ANCHOR METHODS. PROVIDE
 INFORMATION FOR INSTALLATION OF DOOR
 AND WINDOW BUCKS.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026