| | BUILDING PLAN REVIEW |
| | PERMIT: 02061385 |
| | ADD: 2301 CENTREPARK WEST |
| | CONT: LEIGHTON MCGINN |
| | TEL: (561)863-4455 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | ******PROVISO****** |
| | |
| | 1)1606.1.4(1) IN WIND BORNE DEBRIS |
| | REGIONS, EXTERIOR GLAZING THAT RECEIVES |
| | POSITIVE PRESSURE IN BUILDINGS SHALL BE |
| | ASSUMED TO BE OPENINGS UNLESS SUCH |
| | GLAZING IS IMPACT RESISTANT OR PROTECTED |
| | WITH AN IMPACT RESISTANT COVERING MEET- |
| | ING THE REQUIREMENTS OF SSTD 12, ASTM |
| | E 1886 AND ASTM E 1996 OR MIAMI-DADE. |
| | |
| | 1) GLAZED OPENINGS LOCATED WITHIN 30 FT |
| | OF GRADE SHALL MEET THE REQUIREMENTS OF |
| | LARGE MISSLE TEST. |
| | |
| | 2) FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORT, SBCCI OR DADE COUNTY |
| | REPORT ARE ACCEPTED. MISSING MULLION |
| | REPORT. PROVIDE BY BUCK INSPECTION. |
| | |
| | 3)1707.4.5.1 MULLIONS OCCURRING |
| | BETWEEN INDIVIDUAL WINDOW AND GLASS |
| | DOOR ASSEMBLIES. TESTING REPORTS ARE |
| | REQUIRED BY AN APPROVED TESTING |
| | LABORATORY OR BE ENGINEERED. |
| | |
| | 4)1707.4.5.2 MULLIONS SHALL BE DESIGN- |
| | ED TO TRANSFER THE DESIGN PRESSURE LOADS |
| | APPLIED BY THE WINDOW OR DOOR ASSEMBLIES |
| | TO THE ROUGH OPENING SUBTRATE. MULLIONS |
| | THAT ARE TO BE PART OF A LARGE MISSLE |
| | SYSTEM ARE REQUIRED TO BE CLIPPED. |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |