| Plan Review Notes For Permit 02061278 |
| Permit Number |
02061278 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-07-08 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | | | | PLEASE NOTE THE FOLLOWING DISCREPANCIES | | | ON THE DRAWINGS, MAKE ANY NECESSARY | | | CHANGES AND RESUBMIT FOR REVIEW. | | | | | | 1} THE GROUNDING SYSTEM SHOWN AT "A" | | | PANEL SHOULD BE AT THE FIRST MEANS OF | | | DISCONNECT PER 250-24(A)(1). | | | | | | 2} PLEASE NOTE THAT THE #2/0 FEEDERS TO | | | PANEL "B" ON THE RISER DIAGRAM DO NOT | | | CORRELATE WITH THE #6'S SHOWN ON PANEL | | | SCHEDULE "A". | | | | | | 3} THE #2 FEEDERS FROM THE MAIN | | | DISCONNECT TO PANEL "A" DO NOT COMPLY | | | WITH 310-15(B)(6) FOR A 200 AMP OCP. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL: | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/659-8096 EXT. 8392 |
|