Plan Review Notes
Plan Review Notes For Permit 02061272
Permit Number 02061272
Review Stop E
Sequence Number 1
Notes
Date Text
2002-07-05 00:00:00PROVISO
 ~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE NOTE THE FOLLOWING
 CHANGES/ADDITIONS TO THE PLANS MUST BE
 MADE FOR CODE COMPLIANCE:
  
 1} THE #6 EQUIPMENT GROUND RUNNING FROM
 THE METER TO THE FIRST MEANS OF
 DISCONNECT MUST NOT BE RAN AS IT WOULD
 CREATE A PARALLEL PATH TO GROUND WITH
 THE NEUTRAL(GROUNDED
 CONDUCTOR).250-24(A)(5).
  
 2} PANEL "A" IS MARKED AS MAIN &
 MLO,PLEASE CLARIFY.
  
 3} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12
  
 4} PLEASE NOTE THAT THE SWITCH AT THE
 TOP OF THE STAIR CONTROLLING THE STAIR
 LIGHTS SHOULD BE A 3-WAY.
  
 5} THE WALL BETWEEN BEDROOM AND MECH.
 ROOM DOORS IN BEDROOM #3 NEEDS A RECEPTA
 CLE PER 210-52(A)(1)(A).
  
 6} A RECEPTACLE NEEDS TO BE ADDED IN
 BEDROOM #3 ON THE NORTH WALL
 PER 210-52(A)(1).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL:
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT. 8392