| Plan Review Notes For Permit 02061272 |
| Permit Number |
02061272 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-07-05 00:00:00 | PROVISO | | | ~~~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE NOTE THE FOLLOWING | | | CHANGES/ADDITIONS TO THE PLANS MUST BE | | | MADE FOR CODE COMPLIANCE: | | | | | | 1} THE #6 EQUIPMENT GROUND RUNNING FROM | | | THE METER TO THE FIRST MEANS OF | | | DISCONNECT MUST NOT BE RAN AS IT WOULD | | | CREATE A PARALLEL PATH TO GROUND WITH | | | THE NEUTRAL(GROUNDED | | | CONDUCTOR).250-24(A)(5). | | | | | | 2} PANEL "A" IS MARKED AS MAIN & | | | MLO,PLEASE CLARIFY. | | | | | | 3} PLEASE LIST THE REQ'D ARC | | | FAULT PROTECTED CIRCUITS ON PANEL | | | SCHEDULE OR NOTE ON PLANS FOR BRANCH | | | CIRCUIT PROTECTION. PER 210-12 | | | | | | 4} PLEASE NOTE THAT THE SWITCH AT THE | | | TOP OF THE STAIR CONTROLLING THE STAIR | | | LIGHTS SHOULD BE A 3-WAY. | | | | | | 5} THE WALL BETWEEN BEDROOM AND MECH. | | | ROOM DOORS IN BEDROOM #3 NEEDS A RECEPTA | | | CLE PER 210-52(A)(1)(A). | | | | | | 6} A RECEPTACLE NEEDS TO BE ADDED IN | | | BEDROOM #3 ON THE NORTH WALL | | | PER 210-52(A)(1). | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL: | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561/659-8096 EXT. 8392 |
|