| 2002-08-30 00:00:00 | SECOND CHECKLIST: |
| | 1-SECOND FLOOR FRAMING PLAN: REVISE DET. |
| | 5/S3. CONNECTOR SPECIFIED IS A LIGHT |
| | GAUGE PURLIN HANGER NOT A HANGER FOR |
| | A GIRDER TRUSS. ALSO, USP HL210 HAS NO |
| | UPLIFT CAPACITY. SEE USP CATALOGUE. |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| | 2-DETAIL 5/S3: PROVIDE COMPLETE SPECS |
| | FOR GABLE END INSTALLATION. SPECIFY |
| | ALL CONNECTORS AND HOW IS THE TRUSS |
| | ATTACHED TO PROVIDE CONTINUITY. SEE |
| | SECTION 2313.4 FBC 2001. |
| | ALSO, SEE TABLE 2306.1 CITY AMENDMENTS |
| | TO FBC FOR NAIL TYPE AND SPACING. |
| | (8D RING SHANK AT 25' MEAN ROOF HT.) |
| | 3-REVISE TRUSS CONNECTOR SCHEDULE TO |
| | MATCH PUBLISHED VALUES BY USP. |
| | SCHEDULE WAS NOT PROPERLY REVISED. THE |
| | NAIL TYPE WAS CHANGED TO 10DX1 1/2 BUT |
| | VALUES GIVEN ARE FOR 10D NAILS. |
| | **PROVIDE ACTUAL ENGINEERING CALCS FOR |
| | UPLIFT VALUES NOT PUBLISHED BY USP. |
| | 4-NEED RECORDED NOTICE OF COMMENCEMENT. |
| | 5-WINDOW BY ENTRY PORCH TO BE SHOWN AS |
| | DOTTED LINES ON LEFT ELEVATION, SHEET |
| | A-4. OTHERWISE, IT REPRESENTS THAT THE |
| | WINDOW IS ON THE ZERO LOT LINE WALL. |
| | 6-PROVIDE GENERAL SPECIFICATIONS FOR |
| | REQUIRED FIREBLOCKING AT ALL CONCEALED |
| | SPACES AS REQ'D BY SEC. 2305.1.4 FBC. |
| | 7-PROVIDE COMPLETE AND CORRECT INFO. FOR |
| | STORM SHUTTERS OR APPLY FOR SEPARATE |
| | PERMIT. |
| | **KEY PLAN & INSTALLATION SCHEDULE DON'T |
| | MATCH PLANS. |
| | **PRODUCT APPROVAL SUBMITTED REQUIRES |
| | ENGINEER TO SIGN AND SEAL DRAWINGS AND |
| | REQUIRES ADDITIONAL ENGINEERING FOR |
| | SPECIFIC MOUNTING CONDITIONS. SEE |
| | LIMITATIONS ON PAGE 4 OF 4 OF PRODUCT |
| | APPROVAL REPORT. |
| | 8-SHEET S3: ROOF SHEATHING SPECS SHOWN |
| | IN SECTION 5 AND DIAPHRAGM SCHEDULE |
| | DON'T MATCH. REVISE AS REQUIRED. |
| | 9-GARAGE DOOR STRUCTURAL BUCK DETAIL: |
| | SPECIFY LENGTH OF ANCHOR BOLTS AND |
| | REQUIRED WASHER. SEC. 104.2.1.2 CITY |
| | AMENDMENTS AND SEC. 1606 FBC 2001. |
| | 10-DRAWINGS SUBMITTED SHOW GARAGE ON THE |
| | RIGHT HAND SIDE, WHILE SURVEY SHOWS |
| | GARAGE ON THE LEFT HAND SIDE. CLARIFY |
| | TO AVOID CONFLICTS WITH ZONING. |