| Date |
Text |
| 2002-08-13 00:00:00 | DENIED BY BUILDING |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) THE TOTAL AREA LISTED ON SHEETS C1 & |
| | A1 IS INCORRECT. CHECK THE ADDITION AND |
| | CORRECT. |
| | |
| | 3)ONE HOUR RATED GLASS BLOCK IS REQUIRED |
| | AT THE ZERO LOT LINE. PROVIDE UL |
| | SPECIFICATIONS FOR A ONE HOUR FIRE RATED |
| | GLASS BLOCK ASSEMBLY. THE GLASS BLOCK IS |
| | ALSO LOCATED IN A HAZARDOUS LOCATION AND |
| | MUST COMPLY WITH FBC 2405.2.2 AND HAVE A |
| | MINIMUM UNIFORM FACE THICKNESS OF 0.25". |
| | PLEASE SUBMIT MANUFACTURER'S SPECS. THAT |
| | INDICATE FACE THICKNESS OF GLASS BLOCK. |
| | |
| | 4)FL BLDG 1909.3 (EXEPTION# 2) |
| | CONCRETE SLABS ON GRADE CONTAINING 6X6/ |
| | W1.4XW1.4 WELDED WIRE REINFORCEMENT |
| | FABRIC LOCATED IN THE MIDDLE TO THE |
| | UPPER 1/3RD OF THE SLAB SHALL BE SUP- |
| | PORTED BY APPROVED MATERIALS OR SUPPORTS |
| | AT SPACING NOT TO EXCEED 3 FT OR IN |
| | ACCORDANCE WITH MANUFACTURER'S SPEC. |
| | PLEASE INDICATE THIS ON THE PLANS. |
| | |
| | 5) PLEASE CHANGE NOTE 6 ON A-2 TO REFER |
| | TO THE 2001 FLORIDA PLUMBING CODE. |
| | |
| | 6) NUMBER 14 UNDER SECTION AND DETAILS |
| | ON SHEET A-5 INDICATES 3"X24" SCREEN |
| | VENTS AND THE SOFFIT VENT CALCS ON A-3 |
| | LIST 6"X24" VENTS. PLEASE CLARIFY. |
| | |
| | 7) NOTE 3 ON S-2 IS FOR A 110 MPH WIND |
| | VELOCITY AND THE CITY OF WPB IS LOCATED |
| | IN A 140 MPH WIND ZONE. PLEASE CORRECT. |
| | |
| | 8) THE FOUNDATION THICKNESS IS SHOWN ON |
| | THE SECTIONS ON A-5 AS 18". THE FOOTING |
| | SCHEDULE ON S-2 LISTS IT AS 16". PLEASE |
| | CLARIFY. |
| | |
| | 9) SHEET S-2 HAS A TAG FOR F14, WHICH IS |
| | FOR A STEEL COLUMN AND SHOULD BE F16. |
| | |
| | 10) ON SHEET S-2, THERE IS A F5 TAG, |
| | HOWEVER, THERE IS NO F5 SECTION GIVEN. |
| | |
| | 11) PROVIDE SOIL BEARING TEST PER FBC |
| | SECTION 1804.2.2. |
| | |
| | 12) PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR: |
| | - SINGLE HUNG WINDOWS (COVER SHEET DOES |
| | NOT BELONG WITH THE OTHER PAGES, WHICH |
| | ARE EXPIRED) |
| | - STRUCTURAL MULLIONS (EXPIRED) |
| | |
| | 13) STORM PANELS: THERE IS NO |
| | INSTALLATION SCHEDULE. THE OPENING SIZES |
| | ON THE KEY PLAN DO NOT ALL CORRESPOND |
| | WITH THOSE ON THE PLANS. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |