| Date |
Text |
| 2002-07-10 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 CHAPTER 11 |
| | FBC-2001 PLUMBING |
| | |
| | 1) SHT 3.1 REST ROOM # 107. PER 11-4-1-3 |
| | (11), EACH PUBLIC & COMMON TOILET ROOM |
| | SHALL COMPLY WITH 11-4.2.22. OTHER TOI- |
| | LET ROOMS PROVIDED FOR USE OF OCCUPANTS |
| | OF SPECIFIC SPACES, (I.E., A PRIVATE |
| | TOILET ROOM FOR THE OCCUPANT OF A PRIV- |
| | ATE OFFICE) SHALL BE ADAPTABLE. SHOW |
| | BACKING FOR GRAB BARS & SHR SEAT, AND |
| | LOCATION FOR CONTROLS. ALSO GRAB BARS |
| | FOR W/C. |
| | 2) SHT P.1 PLUMBING NOTES #1 SUBMIT MAN- |
| | UFACTURE INFORMATION FOR PRODUCT APPROV- |
| | AL FOR STEAM UNIT. SHOW PAN DRAIN LINE |
| | & T/P RELIEF VALVE DISCHARGE LINE AND |
| | LOCATION OF TERMINATION FOR EACH. SEE |
| | NOTE FOR PLENUM RATING REQUIRED FOR ALL |
| | MATERIALS IN CEILING. |
| | 3) SHTS P.1 & P.2 WATER HEATER DETAIL/ |
| | PLUMBING FIXTURE SCHEDULE, FUNNEL FLOOR |
| | DRAINS NOT APPROVED. ALL INDIRECT WASTE |
| | SHALL DRAIN INTO A FLOOR SINK. 802.3 |
| | 4) SHTS P.1 & P.2 WET VENT FOR TOILET |
| | ROOM #109, ONLY FIXTURES WITHIN THE BATH |
| | ROOM GROUP SHALL CONNECT TO THE WET-VENT |
| | HORIZONTAL BRANCH DRAIN. CAFETERIA SINK |
| | SHALL DISCHARGE DOWNSTREAM OF WET VENT. |
| | 909.1 |
| | 5) SHT P.2 WATER RISER, WATER HAMMER |
| | ARRESTORS ARE REQUIRED AT QUICK CLOSING |
| | VALVES, (W/M - DISHWASHER - ICE MAKER). |
| | PLEASE SHOW W.H.A.'S AT CAFETERIS SINK. |
| | 6) SUBMIT DETAIL FOR HDCP SHOWER. SHOW |
| | COMPLIANCE WITH 11-4.21 AND ALL SUB SEC- |
| | TIONS. |
| | 7) SUBMIT RISER FOR CONDENSATE. SHOW |
| | TERMINATION. IF TIED INTO STORM OR DRY- |
| | WELL, A RELIEF VENT IS REQUIRED. IF |
| | DRAINING ON TO GROUND, MINIMUM OF 12" |
| | FROM BLDG REQUIRED. FBC 1503.4.4 |
| | 8) SUBMIT MANUFACTURE INFORMATION FOR |
| | INSTA-HOT. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 659-8096 EXT 8377 |