| 2002-07-22 00:00:00 | |
| | BUILDING PLAN REVIEW |
| | PERMIT: 02061252 |
| | ADD: 770 NORTHPOINT PARKWAY# 100 |
| | CONT: BUTLER |
| | TEL: 832-9700 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | ARCH: ALAN STRASSLER |
| | TELL: (561) 627-0336 |
| | |
| | 1)704.2.1.4 CORRIDOR PARTITIONS, SMOKE |
| | STOP PARTITIONS, HORIZONTAL EXIT PART- |
| | ITIONS, EXIT ENCLOSURES, AND FIRE |
| | RATED WALLS REQUIRED TO HAVE PROTECTED |
| | OPENINGS SHALL BE EFFECTIVELY AND |
| | PERMANETLY IDENTIFIED WITH SIGNS OR |
| | STENCILING IN A MANNER ACCEPTABLE TO THE |
| | AUTHORITY HAVING JURISDICTION. SUCH IDEN |
| | TIFICATION SHALL BE ABOVE ANY DECORATIVE |
| | CEILING CEILING AND IN CONCEALED SPACES. |
| | SUGGESTED WORDING" FIRE & SMOKE BARRIER |
| | PROTECT ALL OPENINGS". |
| | |
| | 2) TABLE 803.3 MINIMUM INTERIOR FINISH |
| | CLASSIFICATION; PROVIDE INFORMATION |
| | BASED ON INTERIOR FINISH REQUIREMENTS |
| | BASED ON OCCUPANCY |
| | |
| | 3)11-4.1.3(3) GROUND & FLOOR SURFACES |
| | ALONG ACCESSIBLE ROUTES & IN ACCESSIBLE |
| | ROOMS & SPACES SHALL COMPLY WITH |
| | 11-4.5. SEE ADDAAG A4.5.1 (GUIDELINE) |
| | A STATIC COEFFICIENT OF FRICTION OF 0.6 |
| | IS RECOMENDED FOR ACCESSIBLE ROUTES |
| | AND 0.8 FOR RAMPS. |
| | |
| | 4)1204.2 SURROUNDING MATERIALS; |
| | THE WALLS & FLOORS OF ALL PUBLIC REST- |
| | ROOMS SHALL BE LINED WITH NONABSORBANT |
| | MATERIALS TO A HEIGTH OF 4'-0" ABOVE THE |
| | FLOOR. |
| | |
| | 5)1204.3 SHOWERS. SHOWER COMPARTMENTS |
| | SHALL HAVE FLOORS AND WALLS CONSTRUCTED |
| | OF SMOOTH, CORROSION RESISTANT AND NON- |
| | ABSORBENT WATER-RESISTANT MATERIALS TO A |
| | HEIGHT OF NOT LESS THAN 70" ABOVE THE |
| | COMPARTMENT FLOOR AT DRAIN. |
| | |
| | 6) FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORT, SBCCI OR DADE COUNTY |
| | REPORT ARE ACCEPTED. EXTERIOR DOOR @ |
| | CAFETERIA (119A) PROVIDE (2COPIES) OF |
| | EITHER SBCCI OR DADE COUNTY, REPORT TO |
| | SUPPORT TRANSOM ABOVE OR SEPERATE |
| | REPORT REQUIRED. SEE MULLION IF REQUIRED |
| | |
| | 7)1707.4.5.1 MULLIONS OCCURRING |
| | BETWEEN INDIVIDUAL WINDOW AND GLASS |
| | DOOR ASSEMBLIES. TESTING REPORTS ARE |
| | REQUIRED BY AN APPROVED TESTING |
| | LABORATORY OR BE ENGINEERED. |
| | |
| | 8)1707.4.5.2 MULLIONS SHALL BE DESIGN- |
| | ED TO TRANSFER THE DESIGN PRESSURE LOADS |
| | APPLIED BY THE WINDOW OR DOOR ASSEMBLIES |
| | TO THE ROUGH OPENING SUBTRATE. |
| | |
| | |
| | 9)3003.7.1 ACCESS TO MACHINE ROOMS |
| | AND MACHINERY SPACES. A PERMANENT, SAFE |
| | AND CONVENIENT MEANS OF ACCESS TO ELEVA- |
| | TOR MACHINE ROOMS AND OVERHEAD MACHINERY |
| | SPACES SHALL BE PROVIDED FOR AUTHORIZED |
| | PERSONAL. THE MEANS OF ACCESS SHALL NOT |
| | BE THROUGH RESTROOMS, DRESSING ROOMS, |
| | OR TENANT ( INCLUDING OWNER-OCCUPIED) |
| | SPACES. |
| | |
| | LOOK FOR COMMENTS BY THE OTHER PLAN |
| | REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| | ON THE APPLICATION, PLANS, OR ATTACHED |
| | SEPARATELY. WHEN RESUBMITTING PLANS |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A |
| | DESCRIPTION OF THE REVISION MADE, IDEN- |
| | TIFYING THE SHEET OR SPECIFICATION PAGE |
| | WHERE THE CHANGES CAN BE FOUND, WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |
| | JIM WITMER |
| | PLAN REVIEW |
| | TEL: (561)659-8096 EX.8412 |
| | FAX: (561)659-8026 |