| 2002-08-26 00:00:00 | ************BUILDING PROVISO************ |
| | |
| | 1)PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR: |
| | - ARCHED TOP FIXED GLASS WINDOWS AS |
| | SHOWN ON ARCHITECTURAL DRAWINGS |
| | |
| | 2) PROVIDE A SOIL BEARING CAPACITY TEST |
| | REPORT SIGNED AND SEALED BY ENGINEER, |
| | PRIOR TO FIRST INSPECTION. |
| | |
| | 3) PROVIDE MANUFACTURER'S SPECIFICATIONS |
| | AND UL LISTING FOR GLASS BLOCK WHICH |
| | INDICATES A ONE HOUR FIRE RATING. |
| | |
| | 4) PROVIDE (2) PRODUCT APPROVALS, KEY |
| | PLANS AND INSTALLATION SCHEDULES |
| | INDICATING THE SPECIFIC TYPES OF ANCHORS |
| | TO BE USED FOR STORM PANELS. A SEPARATE |
| | PERMIT WITH ADDITIONAL FEES IS REQUIRED. |
| | |
| | 5) PLEASE INDICATE THE INTERNAL PRESSURE |
| | COEFFICIENT ON THE PLANS FOR FUTURE |
| | SUBMITTALS. IT IS + OR - .18 FOR |
| | ENCLOSED STRUCTURES. |
| | |
| | 6) PLEASE CORRECT THE ROOF SHEATHING |
| | NAIL SPACING LISTED ON SHEETS GN-1, S-2 |
| | AND S-3 OF THE PLANS FOR FUTURE |
| | SUBMITTALS. IT IS 6"O.C.INTERMEDIATE AND |
| | 6"O.C.EDGES IN ZONES 1&2 AND 6"O.C. |
| | INTERMEDIATE AND 4"O.C. EDGES IN ZONE 3. |
| | SEE CITY AMENDMENTS TO FBC TABLE 2306.1. |