| 2002-08-12 00:00:00 | BUILDING DENIED |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) FL BLD CODE 1804.2.2 QUESTIONABLE |
| | SOILS, WHERE THE BEARING CAPACITY IS |
| | NOT DEFINETLY KNOWN OR IS IN QUESTION. |
| | PROVIDE A SOIL BEARING REPORT. |
| | |
| | 3) THE SOIL STATEMENT ON SHEET S1 STATES |
| | THAT A SEALED LETTER FROM THE ENGINEER |
| | OF RECORD WILL BE SUBMITTED ATTESTING |
| | THAT THE SITE HAS BEEN OBSERVED AND THE |
| | FOUNDATION CONDITIONS ARE SIMILAR TO |
| | THOSE UPON WHICH THE THE DESIGN HAS BEEN |
| | BASED. |
| | |
| | 4) THE BONUS ROOM IS REQUIRED TO BE |
| | PERMANETLY MARKED ON THE PLANS THAT IT |
| | IS NOT TO BE USED FOR SLEEPING PURPOSES |
| | AND THE ROOM CAN NOT HAVE A CLOSET. |
| | OPENINGS FROM A GARAGE DIRECTLY INTO A |
| | ROOM USED FOR SLEEPING PURPOSES IS NOT |
| | PERMITTED PER 2001 FBC SEC.411.2.8. |
| | |
| | 5) THE WINDOW (H) IN THE FIRST FLOOR |
| | BATHROOM IS REQUIRED TO HAVE TEMPERED |
| | GLASS PER FBC 2405.2.1 (2). |
| | |
| | 6) INDICATE ON THE PLANS THAT THE BONUS |
| | ROOM WALLS ARE INSULATED. |
| | |
| | 7) PLEASE CHANGE NOTE 6 UNDER GENERAL |
| | NOTES ON SHEET A2 TO REFERENCE THE 2001 |
| | FLORIDA PLUMBING CODE. |
| | |
| | 8) THE CONDITIONED AREA LISTED ON THE |
| | ENERGY CALCULATIONS DIFFERS FROM THE |
| | A/C AREA GIVEN ON THE PLANS. PLEASE |
| | CORRECT. |
| | |
| | 9) SHEET S-2 INDICATES A P3 COLUMN BELOW |
| | THE FLOOR TRUSSES,HOWEVER, NOTHING IS |
| | SHOWN AT THIS LOCATION ON THE FOUNDATION |
| | PLAN ON S-1. PLEASE CLARIFY. SHEET A-1 |
| | INDICATES A STRUCTURAL COLUMN,#33 IN THE |
| | KEY NOTES AT THIS LOCATION. |
| | |
| | 10) FL BLDG 1909.3 (EXEPTION# 2) |
| | CONCRETE SLABS ON GRADE CONTAINING 6X6/ |
| | W1.4XW1.4 WELDED WIRE REINFORCEMENT |
| | FABRIC LOCATED IN THE MIDDLE TO THE |
| | UPPER 1/3RD OF THE SLAB SHALL BE SUP- |
| | PORTED BY APPROVED MATERIALS OR SUPPORTS |
| | AT SPACING NOT TO EXCEED 3 FT OR IN |
| | ACCORDANCE WITH MANUFACTURER'S SPEC. |
| | PLEASE INDICATE ON PLANS. |
| | |
| | 11) 2305.2.2 FLOOR/CEILING ASSEMBLIES |
| | SINGLE FAMILY DWELLINGS. IN FLOOR/CEIL- |
| | ING ASSEMBLIES SEPERATING USEABLE SPACE |
| | INTO 2 OR MORE APPROXIMATE AREAS WITH NO |
| | AREA GREATER THAN 500 SQ FT. DRAFTSTOP- |
| | PING SHALL BE PROVIDED PARALLEL TO THE |
| | MAIN FRAMING MEMBERS. PLEASE INDICATE |
| | THE LOCATIONS AND MATERIALS THAT WILL BE |
| | USED ON THE PLANS. |
| | |
| | 12) SECTIONS #1 AND #3 ON S-2 SHOW A |
| | CONCRETE TIE BEAM WITH FOUR REINFORCING |
| | BARS. THE REST OF THE PLANS INDICATE |
| | SINGLE BEAM BLOCK WITH ONE BAR. PLEASE |
| | CLARIFY. |
| | |
| | 13) PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR: |
| | - DOUBLE ENTRY DOORS (THE ONES SUBMITTED |
| | ARE ILLEGIBLE) |
| | - SINGLE HUNG WINDOWS (THE COVER SHEET |
| | DOES NOT MATCH THE REST OF THE PAGES, |
| | WHICH ARE EXPIRED) |
| | - MULLIONS (EXPIRED) |
| | |
| | 14) STORM PANELS: NO INSTALLATION |
| | SCHEDULE WAS SUBMITTED. THE KEY PLAN IS |
| | FOR A GARAGE LEFT MODEL AND THIS IS A |
| | GARAGE RIGHT MODEL. THE OPENING SIZES |
| | ON THE PLANS DIFFER FROM THOSE ON THE |
| | KEY PLAN. PLEASE CORRECT. |
| | |
| | 15) THE NAILS AND SPACING LISTED FOR THE |
| | FLOOR ON SECTION 2 ON SHEET S-2 DOES NOT |
| | CORRESPOND WITH THE FLOOR DIAPHRAGM |
| | NAILING SPECIFIED IN THE SCHEDULE. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |