| 2002-08-23 00:00:00 | BUILDING PLAN REVIEW | | | ******PROVISO******* | | | | | | 1)PROVIDE (2) CURRENT AND COMPLETE | | | COPIES OF SBCCI OR METRO-DADE PRODUCT | | | APPROVALS FOR: | | | - ARCHED TOP FIXED GLASS WINDOWS. | | | | | | 2) PROVIDE (2) COPIES OF MANFACTURER'S | | | SPECIFICATIONS AND UL LISTING NUMBER FOR | | | A ONE HOUR FIRE RATED GLASS BLOCK | | | ASSEMBLY. | | | | | | 3) PROVIDE (2) PRODUCT APPROVALS, KEY | | | PLANS AND INSTALLATION SCHEDULES | | | INDICATING THE SPECIFIC TYPES OF ANCHORS | | | TO BE USED FOR STORM PANELS. A SEPARATE | | | PERMIT WITH ADDITIONAL FEES WILL BE | | | REQUIRED. | | | | | | 4) PLEASE REVISE THE PLANS FOR FUTURE | | | SUBMITTALS TO INCLUDE THE FOLLOWING | | | INFORMATION: | | | - INDICATE THE APPROPRIATE INTERNAL | | | PRESSURE COEFFICENT.(+ OR - .18 FOR | | | ENCLOSED STRUCTURES) | | | - SPECIFY THE FIREBLOCKING MATERIAL THAT | | | WILL BE USED AT THE TOP AND BOTTOM OF | | | THE STAIR RUN. |
|