| 2002-06-24 00:00:00 | DENIED | | | REFERENCE: FBC-2001 FUEL GAS | | | | | | 1. SUBMIT CALCULATIONS FOR COMBUSTION | | | AIR (IF APPLICABLE) PER FBC-2001 FUEL | | | GAS CODE SEC. 304. | | | 2. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE FBC- | | | 2001 FUEL GAS CODE SEC 402.2. | | | 3) CHECK PIPE SIZES - NEED TO CHANGE | | | SIZE TO EXISTING RANGE, AND NEED 1" FROM | | | METER IF GALVANIZED. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|